GE Industrial Solutions LP 33 Series 30 & 40 kVA Operating Manual User Manual

Page 26

Advertising
background image

Modifications reserved

Page 26/57

OPM_LPS_3UO_30K_40K_0US_V010.doc

Operating Manual LP 33 Series 30 & 40 kVA

6.2.2 Messages

list


Are defined messages:

all the recorded events which are referred to the operation status coherent

with the normal situation of the UPS.

Code

Message

Meaning

4111

RECTIFIER
MAINS OK

Rectifier input mains is again within the admitted tolerance
(voltage, frequency and phase).

4114

UPS SHUTDOWN

(LOW BATT VOLTAGE)

The UPS is in Load OFF status, resulting in Battery supply for the
power supply.

Should the Battery voltage decrease to a value below of the one

set in a parameter, then power supply will shutdown to avoid
damage to the Battery

4119

BATTERY TEST

STARTED

Start of manual or automatic battery test.
Rectifier output voltage is decreased to the value defined by
respective parameter.

4120

BATTERY TEST

STOPPED

End battery test.

End of manual or automatic battery test.
Rectifier output voltage is restored to floating voltage.

4141

ISMAX DETECTION

BOOSTER

Detection of persistent booster (Is) current limitation.

4161

RECTIFIER

ON

Rectifier received the command to switch ON.

4162

RECTIFIER

OFF

Rectifier received the command to switch OFF for:

input mains out of tolerance / EPO / UDC max.

4163

GENERATOR

ON

Customer Interface (X1 / 11, 22) received a Gen set ON signaling.
Operating mode dependent on setting of respective parameters.

4164

GENERATOR

OFF

Customer Interface (X1 / 11, 22) received a Gen set OFF
signaling.

Function bypass enabled dependent on setting of respective

parameter.

4302

INVERTER

CANNOT BE

TURNED ON

Inverter cannot be switched on because one of the following
conditions are still present:
• Overtemperature;
• Low battery voltage;

• Inverter fuses;

• Overload;

• K7 opening failure;
• High battery voltage;

• DC low;
• EPO (Emergency Power Off).

4303

INVERTER

CANNOT BE

TURNED OFF

Inverter cannot be switched OFF, because the load cannot be
transferred on mains (voltage out of tolerance, not

synchronizing, bypass blocked).

4361

INVERTER

ON

The command to start the inverter has been activated on the
control panel.