7.1.6 Restore to normal operation after “EPO – Emergency Power Off”

NOTE !

Make sure the UPS to be status of the activation of “EPO”, i. e. Q1 closed, Q2 open and
the battery fuses F5, F6, F7
(and eventual external fuses in case of external battery)
connected.



View of the panel after pressing the button “EPO”:

All Contactors are open.

Booster, inverter and Static-Switch shutdown.

LP 33 40kVA

APPLICAT. SUPPLY OFF

= 0%



1. Reset the buttonEPO”.

Press Alarm, to reset alarm and buzzer.

01.01.2005 12:15:45
NR=255 Status=A588

4563:

EMERGENCY OFF

ACTIVATED

2. Reset the UPS by entering the screen:

MENU/COMMAND MENU/INVERTER OFF

COMMAND MENU

INVERTER ON *
INVERTER OFF

The load is supplied by the mains through the automatic
bypass
.

The booster starts automatically.

The LCD screen must display the status:
APPLICATION ON BYPASS

LP 33 40kVA
APPLICATION ON BYPASS

= 70%

3. Switch ON the inverter by entering the screen:

MENU/COMMAND MENU/INVERTER ON

COMMAND MENU

INVERTER ON *
INVERTER OFF

The load will be automatically transferred from mains to the
inverter.

The LCD screen must display the status:
APPLICATION ON UPS

LP 33 40kVA

APPLICATION ON UPS

= 70%

END OF PROCEDURE