Vent installation, Warning – Monessen Hearth Direct Vent Gas Fireplace CDVR36 User Manual

Page 15

Advertising
background image

69D0023

15

3"

1"

1"

1"

VENT INSTALLATION

A Minimum of 3" Clearance

to the Top Is Required Along

Horizontal Length until Flue

Pipe Penetrates Outside Wall.

A Minimum 1"

Clearance to

Combustibles

Permitted All

Around Flue

at Outside

Wall

Figure 10 -

Combustible Clearances

for Vent Pipe,

CDVT33 and CDVT36

TOP VENT INSTALLATION

WARNING

Horizontal sections of this vent system
require a minimum of 3" clearances to
combustibles at the top of the flue and 1"
clearance at the sides and bottom until the
flue penetrates the outside wall.
A minimum
1" clearance all around the flue is acceptable
at this point of penetration.

Vertical sections of this vent system require
a minimum of 1" clearance to combustibles
on all sides of the pipe.

WARNING

This fireplace must be vented to the outside. The venting system must NEVER be
attached to a chimney serving a separate solid fuel burning appliance. Each gas
appliance must use a separate vent system. Do not use common vent systems.