Vent installation, Warning – Monessen Hearth Direct Vent Gas Fireplace CDVR36 User Manual

Page 20

Advertising
background image

20

69D0023

HOT

HOT

VENT INSTALLATION

4. Apply a bead of non-hardening mastic around the outside

edge of vent cap. Position the vent cap in the center of hole
on the exterior wall with the word “UP” on the vent cap
facing up. Insure proper clearance of 1" to combustibles is
maintained to the flue. Attach the vent cap with four wood
screws supplied. See Figure 17.

WARNING

Do not recess vent
termination into any wall.
This will cause a fire hazard.

NOTE: Replace the wood screws with appropriate
fasteners for stucco, brick, concrete, or other types
of siding.

Figure 17 - Installing Horizontal Termination

REAR WALL VENT INSTALLATION (continued)

Figure 18 - Installing Simpson Vinyl Siding

Standoff and Termination

Apply

Mastic to

All Four

Sides

Vent Cap

Wood

Screw

Cut Vinyl Siding

Away to Fit Standoff

Wood Screw

Termination

Bolt

Apply Mastic to

All Four Sides

Nut

Standoff #950 or 4DT-VS

(not required for

Monessen Termination)

Figure 19 - Installing Firestop on

Horizontal Vent Pipe

Interior Wall

Surface

Firestop

Horizontal

Vent Pipe

Screw

Vent Cap

(Horizontal

Termination)

A vinyl siding standoff must be used with the Simpson or Silkirk Horizontal Termination on vinyl, stucco or wood-clad
exterior walls. Monessen termination does not require a standoff. Apply non-hardening mastic around outside edge of the
standoff instead of the vent cap assembly. See Figure 18.
5. Slide the firestop over the vent pipe before connecting the horizontal run to the vent cap. See Figure 19.
6. The termination should overlap the flue a minimum of 1

1

/

4

" Apply silicone to the outer pipe/termination connection.

Fasten termination with screws provided.

7. Slide the firestop against the interior wall surface and attach with screws. See Figure 19.