Venting installation – Monessen Hearth Direct Vent Gas Fireplace CDVR36 User Manual

Page 19

Advertising
background image

69D0023

19

9

1

/

2

"

(241mm)

9

1

/

2

"

(241mm)

3

3

/

4

"

(92mm)

7

1

/

2

"

(190mm)

Maximum

20"

Top View Flat Installation

REAR (THROUGH THE WALL) APPLICATIONS

When installed as a rear vent unit this appliance may be vented directly to a termination located on the rear wall behind
the appliance
• The maximum horizontal distance between the rear of the appliance and the outside of termination is 20" (508 m). See

Figure 14.

• Only one 45° elbow is allowed in these installations.

VENTING INSTALLATION

1. Rigid vent pipes and fittings have special

twist-lock connections. Assemble the desired
combination of pipe and elbows to the
appliance adaptor.

Twist-lock Procedure: The female ends of
the pipes and fittings have three locking lugs
(indentations). These lugs will slide straight
into matching slots on the male end of adja-
cent pipes and fittings. Push the pipe sections
together and twist one section clockwise
approximately one-quarter turn until the sec-
tions are fully locked. See Figure 15.

2. Locate and cut the vent opening in the wall.

For combustible walls first frame in opening.

Combustible Interior Walls:

Cut a 11

1

/

2

"H x

9

1

/

2

" W hole through the interior wall.

Combustible Exterior Walls:

Cut a 9

1

/

2

"H

x 9

1

/

2

"W square hole through the exterior

wall frame. See Figure 16.

Noncombustible Walls:

Hole opening should

be 7

1

/

2

" (190 mm) in diameter.

3. The center of the hole should line up with the

center line of the horizontal rigid vent pipe
end. Allow

1

/

4

" minimum rise per foot. See

Figure 16.

Figure 14 - Rear Vent Application,

Maximum Horizontal Distance

Figure 16 - Exterior Wall Framing Dimensions

Note: Horizontal runs of vent
must be supported every three
feet (914 mm). Use wall straps
for this purpose.

Figure 15 - Rigid Vent Pipe Connections

Female

Locking Lugs

Male Slots