Troubleshooting – Monessen Hearth Direct Vent Gas Fireplace CDVR36 User Manual

Page 41

Advertising
background image

69D0023

41

STANDING PILOT IGNITION

TROUBLESHOOTING

SYMPTOM

POSSIBLE CAUSE

ACTION

1. Spark

ignitor

will not light
pilot after
repeated trig-
gering of
piezo.

A. Wire disconnected.

B. Defective ignitor.

C. No gas or low gas pressure.

D. No Propane/LPG in tank

A. Open door and check to make sure wire is connected to ignitor.
B. Check for spark at electrode and pilot. If no spark and electrode

wire is properly connected, replace pilot assembly.

C. Check remote/manual shut off valve from fireplace. Low pressure

can be caused by bent lines, restricted lines, low pressure line
pressure. Consult with plumber or gas supplier.

D. Check Propane/LPG tank. Refill tank.

2. Pilot will not

stay lit after
carefully fol-
lowing light-
ing instruc-
tions.

A. Defective thermocouple

B. Defective valve

A. Check that thermocouple flame impinges on thermocouple. Clean

and/or adjust pilot for maximum flame impingement. Ensure that
the thermocouple connection at the gas valve is fully inserted and
tight.

Disconnect the thermocouple from the valve, place one millivolt

lead wire on the tip of the thermocouple and the other meter lead
wire on the thermocouple copper lead. Start the pilot and hold the
valve knob in. If the millivolt reading is less than 15 mV, replace
pilot assembly.

B. If thermocouple is producing more than 15 mV, replace faulty

valve.

3. Pilot

burning,

valve knob
turned to
“ON”, switch
is turned to
“ON” or “RS”,
but burner will
not ignite.

A. Defective switch, wall switch,

remote control or wire

B. Pilot flame too small

C. Defective or malfunctioning ther-

mopile

D. Defective valve

A. Check switch and wire for proper connection. Place jumper wires

across terminals of switch. If burner comes on, replace defective
switch.If the switch is OK, repeat the same procedure on remote
control If burner comes on, replace remote control.

Place jumper wire across wire at gas valves (terminals marked TH

and TP/TH). If burner comes on, wires are faulty or connections
are bad. Replace wire.

B. If pilot flame is not close enough to the thermopile, adjust pilot

flame.

C. Check thermopile wire connections to make sure all are tight and

that the thermopile is fully inserted into pilot assembly. Check
thermopile with a millivolt meter. Connect leads to TP and TP/TH
terminals on the control valve. If meter reading is below 325 mV,
replace pilot assembly.

D. Turn valve knob to “On” and switch to “ON.” Take a reading at

the thermopile leads (TP & TP/TH) on the valve. If the meter
reads greater than 175 mV and the burner does not light, replace
defective valve.

4. Frequent

pilot

outage prob-
lem.

A. Pilot flame may be too high or too

low, causing pilot safety to drop
out

A. Clean and adjust the pilot flame for maximum flame impingement

on thermocouple.

5. The pilot and

main burner
extinguish
while in oper-
ation

A. Inner vent pipe leaking exhaust

gases back into system

B. Horizontal vent improperly pitched

C. Improper vent cap installation

A. Check for flue product leak. Replace defective pipe section.

B. Check horizontal-venting piping is running upward 1/4" per foot.

Do not run the pipe level or downward.

C. Check for proper installation and freedom from debris or blockage