Ldvr series direct vent gas fireplace, Rear wall installation twist lock pipe – Majestic Appliances 36LDVR User Manual

Page 13

Advertising
background image

13

LDVR Series Direct Vent Gas Fireplace

10007317

DVR584-600

Rear vent no elbows

2/99 djt

20"

(508mm)

Top View

Straight Venting

FP836

Rear Vent-Top View

11/21/98

20"

(508mm)

Max.

REAR VENT-TOP VIEW

20"

(508mm)

Max.

Top View

Rear Vent Corner Installation

Fig. 14 Rear vent applications, one 45° elbow.

45°

45°

Rear Wall Installation

Twist Lock Pipe

STEP 1
Locate vent opening on the wall. To locate hole center

consult with appropriate fireplace dimensions, Page 4.

Frame as shown below.
NOTE: When using flex vent, the opening will have to

be measured according to the 1/2” (13 mm) rise in 12”

(305 mm) vertical run.
Combustible Walls (Fig. 15): Cut a 10³⁄₈”H x 9³⁄₈” W

(264 x 240mm) hole through the exterior wall and frame

as shown.
Noncombustible Walls (Fig. 15): Hole opening must

be 7¹⁄₂” (190mm) in diameter.
STEP 2
Measure wall thickness and cut zero clearance sleeve

parts to proper length (MAXIMUM 12”/305mm). Assem-

ble sleeve and attach to firestop with #8 sheet metal

screws (supplied). (Fig. 16)

VO584-100

Vent Opening

2/99 djt

Vent Opening for Combustible Wall

9³⁄₈”

(240mm)

10³⁄₈”

(264mm)

Fireplace Hearth

Framing

Detail

Opening for Noncombustible Wall

7¹⁄₂”

(190mm)

VO584-100

Fig. 15 Locate vent opening on wall.

ZCS101

Zero Clearance Sleeve

3/11/99 djt

Max. Length

12” (305mm)

#8 Screws (2)

#8 Screws

(2)

Adjustable

Zero Clearance

Sleeve

#8

Screws

(2)

Adjustable Zero Clearance Sleeve

ZCS101

Fig. 16 Adjustable zero clearance sleeve.

Firestop

STEP 3
Measure from the fireplace collar or elbow face to face

of outside wall (add 2” for vent pipe overlap). Mark

pipes and cut to length. It is very important that the two

pipes are flush with the outside wall once the fireplace

is in its final location. (Fig. 17)
STEP 4
Slip 4” and 7” pipes onto respective flue collars. Make

sure to fix to the fireplace collar the 4” pipe with three

(3) screws before fixing the 7” pipe on the 7” collar.

Both pipes must be on a level plane. (Fig 18)
STEP 5
Guide the vent termination 4” collar into the 4” pipe then

the 7” collar into the 7” pipe. Do not force the venting

into position. If the pipes do not line up with the termi-

nation collars, disassemble pipes and reattach to the

fireplace collar. (Fig. 18)
STEP 6
Secure fireplace to floor through floor holes and adjust-

able frame drywall strip (nailing flange) to frame. (Refer

to Framing & Finishing Section).