LDVR Series Direct Vent Gas Fireplace

10007317

CFM133

DVR Series Typical corner install

2/26/01 sta

Zero

Clearance

Sleeve

Firestop

CFM133

Fig. 17 Firestop and zero clearance sleeve in place.

FP1005

Side View Vent Termination

1/25/00 djt

Finished Wall

Vent Termi-

nation

FP1005

Fig. 18 Side view of final unit location.

Vertical Sidewall Applications

Since it is very important that the vent-

ing system maintain its balance between

the combustion air intake and the flue

gas exhaust, certain limitations as to vent

configurations apply and must be strictly

adhered to.

The Vent Graph shows the relationship between vertical

and horizontal side wall venting and will help to deter-

mine the various dimensions allowable.

Minimum clearance between vent pipes

and combustible materials is 1”(25mm) on

top, bottom and sides unless otherwise

noted.

When vent termination exits through foundations less

than 20” below siding outcrop, the vent pipe must

flush up with the siding. It is always best to locate the

fireplace in such a way that minimizes the number of

offsets and horizontal vent length.
The horizontal vent run refers to the total length of vent

pipe from the flue collar of the fireplace to the face of

the outer wall.

Rear Wall Vent Installations -

Flex Vent Pipe

Follow Steps 1 and 2 on Page 13.

Step 3

Install the 4” (102mm) flex vent pipe to the appliance

collars described in “General Information Assembling

Vent Pipes”, Page 11. If the installation requires a 45°

angle, grasp the vent pipe close to the appliance collar

and bend to 45°. DO NOT exceed 45°. (Fig. 19)

Install the 7” vent pipe in the same manner as Step 2.

NOTE: There must be a 1” (25mm) rise in a 24”

(610mm) length of flex vent.

Step 4

Assemble the flex vent to the collars on the termination

as you did on the appliance.

FP1473

corner flex install

4/04 djt

Termination

Flex Section

Appliance Collars

FP1473

Fig. 19 Grasp the vent pipe close to the collar and bend to

45° angle. Do not exceed 45°.

FP1472

rise in length

4/04 djt

FP1472

Fig. 20 There must be a 1/2” rise per foot length.

Rise