LDVR Series Direct Vent Gas Fireplace

10007317

•IMPORTANT• Minimum clearance between vent

pipes and combustible materials is one (1”) inch (25 mm)

on bottom, sides and top.

Twist Lock Vent Starter Kit 7TDVSK, plus

Transition Elbow 7TDVRT90 must be used

in Vertical Sidewall installations. The 4”

pipe must be centered inside the 7” pipe

coming off the transition elbow.

Canadian & USA Installations:

The venting system must conform with local codes, or

in the absence of local codes, with National Fuel Gas

Code, ANSI Z223.1/NFPA 54 - latest edition, or CSA

B149.1 Installation Code.
Only CFM Corporation venting components specifically

approved and labelled for this fireplace may be used.

Maximum

3' (914mm)

7TDVRT90

Elbow

CFM142

Venting

2/2/01 sta

CFM142

Fig. 22 Maximum horizontal vent run.

18” (45cm). This does not apply if the 45° elbows

are installed on the vertical part of the vent system.

The maximum number of elbow degrees in a system

is 270°. (Fig. 24)

Example: According to the chart the maximum hori-

zontal vent length in a system with a 7.5ʼ (2.3m) ver-

tical rise is 20ʼ (6 m) and if a 90° elbow is required in

the horizontal vent it must be reduced to 17ʼ (5.2 m).

In Figure 23 Dimension A plus B must not be greater

than 17ʼ (5.2 m).

The maximum number of 45° elbows permitted per

side wall installation is two (2). These elbows can be

installed in either the vertical or horizontal run.

For each 45° elbow installed in the horizontal run,

the length of the horizontal run MUST be reduced by

V584-201

Horizontal Run

2/99 djt

10 ft.

(3048 mm)

7 ft. 6 in.

(2286 mm)

7 ft.

(2134 mm)

CFM147

Fig. 23 Maximum vent run with elbows.

90° Elbow = 3 ft.

A + B = 17 ft. (Max.)

CFM141

2/2/01 sta

Maximum

20 ft. (6.1m)

7.5'

(2.3m)

7TDVRT90

Elbow

15 ft.

(4572mm)

48"

(1.2m)

12"

(305mm)

Vertical Dimension

7¹⁄₂ʼ Minimum When

Horizontal Run is

20ʼ

CFM141

Fig. 21 Maximum number of 90° elbows is three (3).

Horizontal plane means no vertical rise exists on this

portion of the vent assembly.

The maximum horizontal vent run is 20 ft. (6.1m)

when the vertical vent rise is 7¹⁄₂ ft. (2.3m). (Fig. 21)

The maximum number of 90° elbows per side wall

installation is three (3).

If a 90° elbow is used in the horizontal vent run

(level height maintained) the maximum horizontal

vent length is reduced by 36” (914 mm). (Fig. 22)

This does not apply if the 90° elbows are used to

increase or redirect a vertical rise. (Fig. 23)

1

2

3

4

1 + 2 + 3 + 4 = 270

o

CFM132

Insert Rear Vent Sidewall

2/26/01 sta

CFM132

Fig. 24 Maximum number of elbows.

Example:

Elbow 1 = 90˚

Elbow 2 = 45˚

Elbow 3 = 45˚

Elbow 4 = 90˚

Total angular variation = 270˚