LDVR Series Direct Vent Gas Fireplace

10007317

Troubleshooting - Honeywell Millivolt Valve

Remove Window Frame Assembly Before Service Work

START

CHECK

Gas Supply On

Pilot Lights With Piezo

Ignitor

Lockout Has Engaged. Wait 60

Seconds And Try Again.

For Spark At Electrode While

Depressing Piezo

1/8" Gap To Pilot Hood Needed.

All Wiring Connections

Replace Piezo Ignitor

Supply Line Hooked Up

Shutoff Valve Open

Pilot Stays Lit

For Air In The Lines

Thermopile Needs A Min.

325mv. Adjust Pilot Flame

Height.

All Wiring Connections

Replace Thermopile

Thermocouple Needs A Min. Of

14mv

Defective Valve. Turn To Pilot,

Meter Should Read Greater

Than 100mv. If Not, Replace.

Pilot Lights Main Burner

Valve Is Turned On

Wall Switch Is Not Turned On.

Watch For Grounded Wires!

Thermopile Needs A Min. 325mv.

Plugged Burner Orifice

SYSTEM OK

YES

NO

NO

NO

NO

YES

YES

YES