22

17

MRS input selection

0, 2

1

0

29

18

High speed maximum frequency

120 to 400Hz

0.01Hz

120/60Hz

*1

28

19

Base frequency voltage

0 to 1000V, 8888, 9999

0.1V

9999

28

Acc

eler

ation

and

de

cel

er

at

ion

time

s

20

Acceleration/deceleration reference
frequency

1 to 400Hz

0.01Hz

60Hz

28

21

Acceleration/deceleration time
increments

0, 1

1

0

28

St

al

l

pr

eve

nt

ion

22

Stall prevention operation level

0 to 150%, 9999

0.1%

120%

30

23

Stall prevention operation level
compensation factor at double speed

0 to 200%, 9999

0.1%

9999

30

Mu

lti-

sp

e

ed

se

tti

ng

24 to 27

Multi-speed setting 4 speed to 7 speed

0 to 400Hz, 9999

0.01Hz

9999

28

28

Multi-speed input compensation
selection

0, 1

1

0

30

29

Acceleration/deceleration pattern
selection

0, 1, 2, 3

1

0

30

30

Regenerative function selection

0, 2/0, 1, 2

*1

1

0

31

Fr

eq

uen

cy

ju

m

p

31

Frequency jump 1A

0 to 400Hz, 9999

0.01Hz

9999

31

32

Frequency jump 1B

0 to 400Hz, 9999

0.01Hz

9999

31

33

Frequency jump 2A

0 to 400Hz, 9999

0.01Hz

9999

31

34

Frequency jump 2B

0 to 400Hz, 9999

0.01Hz

9999

31

35

Frequency jump 3A

0 to 400Hz, 9999

0.01Hz

9999

31

36

Frequency jump 3B

0 to 400Hz, 9999

0.01Hz

9999

31

37

Speed display

0, 1 to 9998

1

0

31

F

re

que

nc

y

de

te

ct

io

n

41

Up-to-frequency sensitivity

0 to 100%

0.1%

10%

31

42

Output frequency detection

0 to 400Hz

0.01Hz

6Hz

31

43

Output frequency detection for reverse
rotation

0 to 400Hz, 9999

0.01Hz

9999

31

Sec

ond

fu

nct

ion

s

44

Second acceleration/deceleration time

0 to 3600/360s

0.1/0.01s

5s

28

45

Second deceleration time

0 to 3600/360s, 9999

0.1/0.01s

9999

28

46

Second torque boost

0 to 30%, 9999

0.1%

9999

28

47

Second V/F (base frequency)

0 to 400Hz, 9999

0.01Hz

9999

28

48

Second stall prevention operation
current

0 to 150%

0.1%

120%

30

49

Second stall prevention operation
frequency

0 to 400Hz, 9999

0.01Hz

0Hz

30

50

Second output frequency detection

0 to 400Hz

0.01Hz

30Hz

31

51

Second electronic thermal O/L relay

0 to 500A, 9999 /
0 to 3600A, 9999

*1

0.01/0.1A

*1

9999

29

M

on

ito

r f

un

cti

o

ns

52

DU/PU main display data selection

0, 5, 6, 8 to 14, 17, 20, 23
to 25, 50 to 57, 100

1

0

32

54

FM terminal function selection

1 to 3, 5, 6, 8 to 14, 17, 21,
24, 50, 52, 53

1

1

32

55

Frequency monitoring reference

0 to 400Hz

0.01Hz

60Hz

32

56

Current monitoring reference

0 to 500/0 to 3600A

*1

0.01/0.1A

*1

Rated inverter

output current

32

Autom

a

tic

re

st

a

rt

fu

n

ctio

ns

57

Restart coasting time

0, 0.1 to 5s, 9999/
0, 0.1 to 30s, 9999

*1

0.1s

9999

33

58

Restart cushion time

0 to 60s

0.1s

1s

33

59

Remote function selection

0, 1, 2, 3

1

0

33

60

Energy saving control selection

0, 4, 9

1

0

34

65

Retry selection

0 to 5

1

0

34

*1