Noise elimination at the analog input, Reset selection, disconnected pu detection, Output function of alarm code – MITSUBISHI ELECTRIC INVERTER FR-F700 User Manual

Page 35: Prevention of parameter rewrite, Prevention of reverse rotation of the motor

Advertising
background image

Features

Standard

Specifications

Outline

Dimension

Drawings

Operation

Panel

Protective

Functions

Options

Instructions

Motor

Compatibility

W

arranty

Inquiry

Peripheral Devices

Why energy

savings?

Te

rminal Connection

Diagram

Te

rminal Specification

Explanation

Parameter

List

Explanations

of

Parameters

36

indicates simple mode parameters and

indicates extended parameters. When setting parameters, refer to the instruction manual (applied) and understand instructions.

Pr.

Pr.

The time constant of the primary delay filter relative to external
frequency command (analog input (terminal 1, 2, 4) signal) can
be set.

Valid for eliminating noise of the frequency setting circuit.
Increase the filter time constant if steady operation cannot be
performed due to noise.
A larger setting results in slower response. (The time constant can
be set between approximately 10ms to 1s with the setting of 0 to 8.)

You can select the reset input acceptance, disconnected PU
(FR-DU07) connector detection function and PU stop function.

Reset selection
⋅ You can select the operation timing of reset function (RES

signal, reset command through communication) input

Disconnected PU detection
⋅ This function detects that the PU (FR-DU07/FR-PU04) has

been disconnected from the inverter for longer than 1s and
causes the inverter to provide an alarm output (E.PUE) and
come to an alarm stop.

PU stop selection
⋅ In any of the PU operation, external operation and network

operation modes, the motor can be stopped by pressing

of

the PU.

At alarm occurrence, its description can be output as a 4-bit
digital signal from the open collector output terminals.
The alarm code can be read by a programmable controller, etc.,
and its corrective action can be shown on a display, etc.

The following table indicates alarm codes to be output. (0: output
transistor off, 1: output transistor on)

You can select whether write to various parameters can be
performed or not. Use this function to prevent parameter values
from being rewritten by misoperation.

This function can prevent reverse rotation fault resulting from the
incorrect input of the start signal.

Noise elimination at the analog
input

Pr.74 Input filter time constant

Reset selection, disconnected PU
detection

Pr.75 Reset selection/disconnected PU detection/PU stop selection

Pr.75

Setting

Reset Selection

Disconnected

PU Detection

PU Stop

Selection

0

Reset input normally
enabled.

If the PU is
disconnected,
operation will be
continued as-is.

Pressing

decelerates the
motor to a stop only
in the PU operation
mode.

1

Reset input enabled
only when the protective
function is activated.

2

Reset input normally
enabled.

When the PU is
disconnected,
the inverter
output is shut
off.

3

Reset input enabled
only when the protective
function is activated.

14

(initial

value)

Reset input normally
enabled.

If the PU is
disconnected,
operation will be
continued as-is.

Pressing

decelerates the
motor to a stop in
any of the PU,
external and
communication
operation modes.

15

Reset input enabled
only when the protective
function is activated.

16

Reset input normally
enabled.

When the PU is
disconnected,
the inverter
output is shut
off.

17

Reset input enabled
only when the protective
function is activated.

Pr.

74

Pr.

75

Output function of alarm code

Pr.76 Alarm code output selection

Pr.76 Setting

Description

0 (initial value)

Without alarm code output

1

With alarm code output (Refer to the following table)

2

Alarm code output at alarm occurrence only (Refer to
the following table)

Operation Panel

Indication

(FR-DU07)

Output of Output Terminals

Alarm Code

SU

IPF

OL

FU

Normal *

0

0

0

0

0

E.OC1

0

0

0

1

1

E.OC2

0

0

1

0

2

E.OC3

0

0

1

1

3

E.OV1 to E.OV3

0

1

0

0

4

E.THM

0

1

0

1

5

E.THT

0

1

1

0

6

E.IPF

0

1

1

1

7

E.UVT

1

0

0

0

8

E.FIN

1

0

0

1

9

E.BE

1

0

1

0

A

E. GF

1

0

1

1

B

E.OHT

1

1

0

0

C

E.OLT

1

1

0

1

D

E.OPT

1

1

1

0

E

E.OP1

1

1

1

0

E

Other than the

above

1

1

1

1

F

* When Pr. 76 = "2", the output terminals output the signals assigned to

Pr.

190 to Pr. 196.

Prevention of parameter rewrite

Pr.77 Parameter write selection

Pr. 77 Setting

Description

0 (initial value)

Write is enabled only during a stop

1

Parameter write is not enabled.

2

Parameter write is enabled in any operation
mode regardless of operation status.

Prevention of reverse rotation of
the motor

Pr.78 Reverse rotation prevention selection

Pr.78 Setting

Description

0 (initial value)

Both forward and reverse rotations allowed

1

Reverse rotation disabled

2

Forward rotation disallowed

Pr.

76

Pr.

77

Pr.

78