Increase cooling fan life, Slip compensation, Input/output phase failure protection selection – MITSUBISHI ELECTRIC INVERTER FR-F700 User Manual

Page 41: Display of the life of the inverter parts

Advertising
background image

Features

Standard

Specifications

Outline

Dimension

Drawings

Operation

Panel

Protective

Functions

Options

Instructions

Motor

Compatibility

W

arranty

Inquiry

Peripheral Devices

Why energy

savings?

Te

rminal Connection

Diagram

Te

rminal Specification

Explanation

Parameter

List

Explanations

of

Parameters

42

indicates simple mode parameters and

indicates extended parameters. When setting parameters, refer to the instruction manual (applied) and understand instructions.

Pr.

Pr.

You can control the operation of the cooling fan (200V class
2.2K or more, 400V class 3.7K or more) built in the inverter.

The inverter output current may be used to assume motor slip to
keep the motor speed constant.

Used to select the stopping method (deceleration to a stop or
coasting) when the start signal turns off.
Used to stop the motor with a mechanical brake, etc. together
with switching off of the start signal.
You can also select the operations of the start signals (STF/STR).

When Pr. 250 is set to "9999" (initial value) or "8888".

When Pr. 250 is set to values other than "9999" (initial value) or "8888".

You can disable the output phase failure protection function that
stops the inverter output if one of the inverter output side (load
side) three phases (U, V, W) opens.
The input phase failure protection selection of the inverter input
side (R/L1, S/L2, T/L3) can be made valid.

Degrees of deterioration of main circuit capacitor, control circuit
capacitor or inrush current limit circuit and cooling fan can be
diagnosed by monitor.
When any part has approached the end of its life, an alarm can
be output by self diagnosis to prevent a fault.
(Use the life check of this function as a guideline since the life
except the main circuit capacitor is calculated theoretically.)

Increase cooling fan life

Pr.244 Cooling fan operation selection

Pr. 244 Setting

Description

0

The cooling fan operates at power on.
Cooling fan on/off control invalid (The cooling
fan is always on at power on)

1 (initial value)

Cooling fan on/off control valid
The fan is normally on during inverter
operation. The fan switches on/off according to
the temperature during a stop of the inverter
whose status is monitored.

Slip compensation

Pr.245 Rated slip

Pr.246 Slip compensation time constant

Pr.247 Constant-output region slip compensation selection

Selection of motor stopping
method and start signal

Pr.250 Stop selection

Pr.250

Setting

Description

Start signal

(STF/STR)

Stop operation

0 to 100s

STF signal: Foward

rotation start

STR signal: Reverse

rotation start

The motor is coasted to a
stop when the preset time
elapses after the start
signal is turned off. The
motor is coasted to a stop
(Pr. 250 - 1000)s after the
start signal is turned off.

1000s to 1100s

STF signal: Start signal
STR signal: Forward/

reverse
rotation signal

9999

STF signal: Foward

rotation start

STR signal: Reverse

rotation start

When the start signal is
turned off, the motor
decelerates to stop.

8888

STF signal: Start signal
STR signal: Forward/

reverse
rotation signal

Pr.

244

Pr.

245 to 247

Pr.

250

Time

ON

OFF

Start
signal

Deceleration starts
when start signal turns off

Deceleration time
(Time set in Pr. 8, etc.)

DC brake

Output frequency

(Hz)

ON

OFF

RUN
signal

OFF

ON

Start signal

Output is shut off when set
time elapses after start signal
turned off

Pr.250

Motor coasts to stop

Time

OFF

RUN signal

Output frequency

(Hz)

ON

Input/output phase failure
protection selection

Pr.251 Output phase failure protection selection

Pr.872 Input phase failure protection selection

Pr. Number

Setting Range

Description

251

0

Without output phase failure protection

1 (initial value)

With output phase failure protection

872

0 (initial value)

Without input phase failure protection

1

With input phase failure protection

252, 253

Refer to the section about Pr. 73 and
other relevant parameters.

Display of the life of the
inverter parts

Pr.255 Life alarm status display

Pr.256 Inrush current limit circuit life display

Pr.257 Control circuit capacitor life display Pr.258 Main circuit capacitor life display
Pr.259 Main circuit capacitor life measuring

Pr.

Number

Setting

Range

Description

255

(0 to 15)

Display whether the control circuit capacitor,
main circuit capacitor, cooling fan, and each
parts of the inrush current limit circuit has
reached the life alarm output level or not.
Reading only

256

(0 to 100%)

Display the deterioration degree of the inrush
current limit circuit. Reading only

257

(0 to 100%)

Display the deterioration degree of the control
circuit capacitor. Reading only

258

(0 to 100%)

Display the deterioration degree of the main
circuit capacitor. Reading only
The value measured by Pr. 259 is displayed.

259

0, 1

(2, 3, 8, 9)

Setting "1" and turning off the power starts the
measurement of the main circuit capacitor life.
When the Pr. 259 value is "3" after powering on
again, the measuring is completed. Read the
deterioration degree in Pr. 258.

260

Refer to the section about Pr. 72.

Pr.

251, 872

Pr.

Pr.

255 to 259

Pr.

Advertising