Resetting the inverter initializes the internal thermal integrated data of the electronic thermal relay function.

*2

The error message shows an operational error. The inverter output is not shut off.

*3

Warnings are messages given before major failures occur. The inverter output is not shut off.

*4

Minor faults warn the operator of failures with output signals. The inverter output is not shut off.

*5

When major failures occur, the protective functions are activated to shut off the inverter output and output the alarms.

*6

The external thermal operates only when the OH signal is set in Pr. 178 to Pr. 189 (input terminal function selection).

Ma

jo

r fa

ilu

re

s

*5

PU disconnection

Appears when a communication error between the PU and inverter occurred, the

communication interval exceeded the permissible time during the RS-485

communication with the PU connecter, or communication errors exceeded the

number of retries during the RS-485 communication.

Retry count excess

Appears when the operation was not restarted within the set number of retries.

Parameter storage devide

alarm

Appears when operation of the element where parameters stored became

abnormal. (main circuit board)

CPU error

Appears during the CPU and peripheral circuit errors.

/
/

Operation panel power

supply short circuit

RS-485 terminals power

supply short circuit

Appears when the RS-485 terminal power supply or operation panel power supply

was shorted.

24VDC power output short

circuit

Appears when terminals PC-SD were shorted.

Output current detection

value exceeded

Appears when output current exceeded the output current detection level set by the

parameter.

Inrush resistor overheat

Appears when the resistor of the inrush current limit circuit overheated.

Communication error

(inverter)

Appears when a communication error occurred during the RS-485 communication

with the RS-485 terminals.

Analog input error

Appears when 30mA or more is input or a voltage (7.5V or more) is input with the

terminal 2/4 set to current input.

Internal circuit error

Appears when an internal circuit error occurred.

Brake transistor alarm

detection

This function stops the inverter output if an alarm occurs in the brake circuit, e.g.

damaged brake transistors. In this case, the inverter must be powered off

immediately. (Internal circuit error for the model 55K or less)