18

Four terminal modules
Note:

Module 1 is connected to terminals 1A, 1B, 1C and 1D
Module 2 is connected to terminals 2A, 2B, 2C and 2D
Module 3 is connected to terminals 3A, 3B, 3C and 3D

Module type

Terminal identity

Possible functions

A

B

C

D

lay: changeover

(2A, 264 Vac max.)

Heating, cooling,or

alarm,

DC control: Isolated

(10V, 20mA max.)

++

−−

Heating, or cooling

24Vdc transmitter supply

+

To power process

inputs

Potentiometer input

100

to 15K

+

0.5Vdc

0V

Motorised Valve

Position feedback

DC retransmission

+

Retrans. of setpoint,

or process value

DC remote input or

Process Value 2

(Module 3 only)

0-10Vdc

RT source

±

100mV

0-20mA

COM

Remote Setpoint

Second PV

Dual output modules

Dual relay

(2A, 264 Vac max.)

Heating + cooling

Dual alarms

Valve raise & lower

Dual Triac

(1A, 30 to 264Vac)

Heating + cooling

Valve raise & lower

Dual logic + relay

(Logic is non-isolated)

+

Heating + cooling

Dual Logic + triac

(Logic is non-isolated)

+

Heating + cooling

Triple logic input and output modules - see ratings on the next page

Triple contact input

Input 1

Input 2

Input 3

Common

Triple logic input

Input 1

Input 2

Input 3

Common

Table 1-2 Four terminal module connections.