Marathon monitors inc – Marathon Computer AACC 2000 User Manual

Page 61

Advertising
background image

Marathon Monitors Inc.

AACC 2000 Carbon Nov. 1, 1997

61

configuration list. ‘

func’ should be set to ‘Vpos’, ‘VAL.L’ must be set to ‘0’ and

VAL.H’ to ‘100’.

Exit from configuration and you are now ready to calibrate the position feedback
potentiometer. Proceed as follows.
1. In Operator level, press the AUTO/MAN button to put the controller in Manual mode.

2. Drive the valve to its fully open position using

.

3. Press

until you get to ‘

ip-List’.

4. Press

to get to ‘

PCAL-OFF’.

5. Press

or

to turn ‘

PCAL’ to ‘on’.

6. Press

and the upper readout indicates ‘

Pot’.

7. Press

or

to get to ‘

Pot-3A.Hi’. (Assuming that the Potentiometer Input

Module is in module position 3.)

8. Press

to go to ‘

GO-no’.

9. Press

or

to see ‘

GO-YES’, which starts the calibration procedure.

10. Calibration is complete when the display returns to ‘

GO-no’.

11. Press

and

together to return directly to the Operator level.

12. The controller should still be in Manual mode.

13. Drive the valve to its fully closed position using

.

14. Press

until you get to ‘

ip-List’.

15. Press

to get to ‘

PCAL-OFF’.

16. Press

or

to turn ‘

PCAL’ to ‘on’.

17. Press

and the upper readout indicates ‘

Pot’.

18. Press

or

to get to ‘

Pot-3A.Lo’

19. Press

to go to ‘

GO-no’.

20. Press

or

to see ‘

GO-YES’, which starts the calibration procedure.

21. Calibration is complete when the display returns to ‘

GO-no’.

22. Press

and

together to return directly to the Operator level.

23. Press the AUTO/MAN button to place the controller in AUTO and the calibration of

the position feedback potentiometer is now complete.