Selecting configuration level

There are two alternative methods of selecting Configuration level:

If you have already powered up, then follow the access instructions given in Chapter

3, Access levels.

Alternatively, press

and

together when powering up the controller. This will

take you directly to the ‘

ConF’ password display.

Password entry

When the ‘

ConF’ display appears, you must enter the

Configuration password (which is a number) in order to gain
access to Configuration level.

Enter the password using the

or

buttons.

The configuration password is set to ‘

2’ when the controller

is shipped from the factory.

Once the correct password has been entered, there is a two
second delay, after which the lower readout will change to

PASS’ indicating that access is now unlocked.

Note: A special case exists if the password has been set to

0’. In this situation, access is permanently unlocked and the

lower readout will always show ‘

PASS’.

Press

to enter configuration.

(If an incorrect password has been entered and the controller

is still ‘locked’ then pressing

at this point will take you

to the ‘

Exit’ display with ‘no’ in the lower readout. Simply

press

to return to the ‘

ConF’ display.)

You will obtain the first display of configuration.