AACC 2000 Carbon Nov. 1, 1997

87

Offset calibration

Offset calibration is used to apply a single fixed offset over the full display range of the
controller.









To calibrate, proceed as follows:

1. Connect the input of the controller to the source device to which you wish to calibrate.

2. Set the source to the desired calibration value.

3. The controller will display the current measurement of the value.

4. If the displayed value is correct, then the controller is correctly calibrated and no

further action is necessary. If it is incorrect, then follow the steps shown below.

Select ‘

FuLL’ access level, as described in Chapter 3.

x 3

Input list header

Press

until you reach the input list header.

Press

until you reach the

CAL’ display.

Calibration type

FACt:

Factory Calibration

USEr:

User Calibration

Use

or

to select ‘

FACt’.

Selecting ‘

FACt’ reinstates the factory

calibration and allows the application of a single
fixed offset.

Press

continued on the next page

Displayed Value

Input

Factory Calibration

Fixed Offset