Marathon monitors inc – Marathon Computer AACC 2000 User Manual

Page 83

Advertising
background image

Marathon Monitors Inc.

AACC 2000 Carbon Nov. 1, 1997

83

Name

Description

Values

Meaning

CAL

CAL

Calibration

In this mode you can
1. Calibrate the instrument using a mV source -

rcAL or ref source cal.

2. Offset the calibration to account for errors in actual sensor

measurement and a ref sensor -

UCAL or user calibration

3. Return to factory set calibration -

FACT or factory set calibration.

rcAL

Calibration
point

nonE

No calibration

PV

Calibrate main Process Value input.

PV.2

Calibrate DC input, or PV 2.

1A.Hi

Calibrate DC output high - Module 1

1A.Lo

Calibrate DC output low - Module 1

2A.Hi

Calibrate DC output high - Module 2

2A.Lo

Calibrate DC output low - Module 2

3A.Hi

Calibrate DC output high - Module 3

3A.Lo

Calibrate DC output low - Module 3

I

NPUT

C

ALIBRATION

For

CAL

=

PV’, or ‘PV.2

’, the following parameters apply.

PV

PV Calibration Value

IdLE

Idle

mv.L

Select 0mV as the calibration
point

mv.H

Select 50mV as the calibration
point

V 0

Select 0Volt as the calibration
point

1. Select calibration value

V 10

Select 10V as the calibration
point

2. Apply specified input

CJC

Select 0

o

C CJC calibration point

3. Press

to step to

GO’

rtd

Select 400

as the calibration

point

HI 0

High impedance: 0Volt cal’n
point

HI 1.0

High impedance: 1.0 Volt cal’n
point

See Note below.

FACt

Restore factory calibration

GO

Start calibration

no

Waiting to calibrate PV point

Goto User
calibration
table-See also
chapter 7

Go to input
Calibation table

Go to
DC Output
Calibration
table