57

Setting the cutback values

The above procedure sets up the parameters for optimum steady state control. If
unacceptable levels of overshoot or undershoot occur during start-up, or for large step
changes in process variable, then manually set the cutback parameters ‘

Lcb’ and ‘Hcb’.

Proceed as follows:

1. Set the low and high cutback values to three proportional bandwidths (that is to say,

Lcb = Hcb = 3 x Pb).

2. Note the level of overshoot, or undershoot, that occurs for large atmosphere changes

(see the diagrams below).

In example (a) increase ‘

Lcb’ by the overshoot value. In example (b) reduce ‘Lcb’ by

the undershoot value.

Example (a)

Example (b)

Where the atmosphere approaches setpoint from above, you can set ‘

Hcb’ in a similar

manner.

Atmosphere

Time

Setpoint

Atmosphere

Undershoot

Setpoint

Overshoot