Marathon monitors inc – Marathon Computer AACC 2000 User Manual

Page 21

Advertising
background image

Marathon Monitors Inc.

AACC 2000 Carbon Nov. 1, 1997

21

Wiring of 2-wire EIA-485 serial communications link

Com

Note:
All resistors are 220 ohm 1/4W carbon composition.
Local grounds are at equipotential. Where equipotential is not available wire into
separate zones using a galvanic isolator.
Use a repeater (KD845) for more than 32 units.

A

B

PC

MMI Universial

Converter

RX

TX

Com

Com

TX

RX

Up to 32 S2000 controllers or
Interface Units may
be included on the network

232

Com

B

A

Com

A

B

Com

A

B

Com

A

B

Local Earth

Local
Ground
Zone 1

Local
Ground
Zone 2

Area 1

Com

A

B

E

F

D

Local
Earth

HE-

HF+

HD

Series 2000
Controller

HE-

HF+

HD

Series 2000
Controller

For reasons of safety
do not connect to
local earth here.

Local
Earth

Local
Earth

Local
Earth

Local
Earth

Local
Earth

HE -

HF+

HD

Series 2000
Controller

Galvanic

Isolation

Barrier

Local
Ground
Zone 1

Local
Ground
Zone 1

Local
Ground
Zone 1

Figure 1-9 EIA-485 wiring

2-wire EIA-485 is a connection which allows up to 32
controllers to be multi-dropped from a single
communications link over a distance of up to 1.2Km.
To ensure reliable operation of the communications
link, (without data corruption due to noise or line
reflections) the connections between the controller
should be made using a twisted pair of wires inside a
screened cable with the connections terminated with
resistors in the manner shown in this diagram.