Marathon monitors inc – Marathon Computer AACC 2000 User Manual

Page 75

Advertising
background image

Marathon Monitors Inc.

AACC 2000 Carbon Nov. 1, 1997

75

Name

Description

Values

Meaning

AA

AA

Alarm relay configuration

id

Identity

rELy

Relay output

Func

Function

nonE

No function

dIG

Digital output

SEnS

Digital output sense

nor

Normal (output energises when
TRUE, e.g. program events)

inv

Inverted (output de-energises
when TRUE, e.g. alarms)

The following digital events appear after

SEnS’. Any one, or more, of the events can be

combined on to the output (see Fig. 6-2) by selecting

YES’ in the lower readout.

1 - - -

Alarm 1 active

YES / no (- - -) = alarm type (e.g. FSL).

2 - - -

Alarm 2 active

YES / no If an alarm has not been

configured

3 - - -

Alarm 3 active

YES / no in ‘AL ConF’ list, then display

will

4 - - -

Alarm 4 active

YES / no differ:- e.g. Alarm 1 = ‘AL 1’.

mAn

Controller in manual mode

YES / no

Sbr

Sensor break

YES / no

SPAn

PV out of range

YES / no

Lbr

Loop break

YES / no

Ld.F

Load failure alarm

YES / no

tunE

Tuning in progress

YES / no

dc.F

Voltage output open circuit, or mA
output open circuit

YES / no

rmt.F

module connection open circuit

YES / no

iP1.F

Input 1 Failure

IMP

Impedance test in progress

burn

Probe burn off in progress

VERi

Probe verification in progress

VFLT

Verification Fault

PFLT

Probe Fault

nw.AL

New Alarm has occurred

YES / no

End

End of setpoint rate limit, or end of
program

YES / no

SYnc

Program Synchronisation active

YES / no