SECTION 3: WIRING AND INSTALLATION

DS2100 User's Manual (Preliminary)

PAGE 3-5

3.1.2 A.C. Input Line Protection

Details of the recommended Line fuses are given in Section 2 of this manual. Alternatively an AC mains Circuit Breaker
(Instantaneous Trip Type) can be used as a protective device provide its ratings are equivalent to the recommended
fuses.

After a power loss to the servo-drive, the motor will continue running until its stored energy is dissipated through
friction alone, or will be stopped by a motor-equipped brake if a brake is available.

It is also recommended to install a contactor rated for the DS2100 input between the line fuses and the EMC filter at the
input of the DS2100 (refer to Figure 3.1). This contactor should be controlled directly by user supplied Emergency Stop
Buttons and other series connected safety switches to remove AC input power in any situation affecting personnel
safety.

3.1.3 Line Filter Requirements

Details of the recommended line filters for each of the DS2100 variants are given in Section 2 of this manual.

WARNING - The supply-disconnecting device (circuit breaker) must be switched to
the OFF position before any service or maintenance activity is commenced.