Internal/external regeneration resistors, Ds2100 user's manual (preliminary) – Moog DS2100 User Manual

Page 44

Advertising
background image

DS2100 User's Manual (Preliminary)

SECTION 3: WIRING AND INSTALLATION

PAGE 3-38

3.10 Internal/External Regeneration (Regen) Resistors – Configurations

Regeneration resistors can be fitted to all DS2100 servo-drives. All external Regen resistors should be mounted to allow
adequate heat dissipation and such that heat from the Regen resistor is not directed to air intakes of other equipment. The
mA size DS2100 is the only size with internal regen. All other drive sizes use external regen only.

DS2100 Regeneration Resistor Options

Model (Size)

Internal Regen

External Regen

Resistance
(

W)

Continuous
Power (W)

Peak Power
(@ 400V

AC

) (kW)

Resistance
(

W)

Continuous
Power (W)

Peak Power
(@ 400V

AC

) (kW)

G361-x003 (

mA) 120

50

4.8

120

50

4.8

G361-x006 (

mA) 120

100

4.8

120

100

4.8

G361-x008 (A)

51

200

12.5

G361-x014 (B)

33

250

19.4

G361-x020 (C)

12

370

53.3

G361-x025 (C)

12

370

53.3

G361-x030 (C)

12

370

53.3

G361-x050 (D)

10

750

64

G361-x060 (D)

Internal Regen is available only on the DS2100

mA

Size.

10

750

64

Table 3.13 Recommended Regeneration Resistors

For EMC purposes, use shielded cable to connect the external Regen resistor to
the DS2100. The length of this cable should be as short as possible. The shields
of these cables should be connected to Chassis Earth using the optional EMC kit
or the panel earth bar. Alternatively, if the cable is required to pass through an
enclosure panel earthed to Chassis Earth, the shield may be earthed to the panel
by use of a 360 degree metal cable gland.

Refer to Section 2 for further safety and EMC requirements for cable
installation.

NOTE - The regeneration resistor (internal and external) are protected by
software. Setting the regen power and resistance parameters, allows the drive to
calculate the maximum allowable duty cycle for the regen transistor. The
software will clamp the regen duty-cycle at this level. If the drive tries to regen
at a greater level, an overvoltage error will occur.

WARNING - External regen resistors are connected to the DS2100 D.C. Bus
voltage that can reach 800 V d.c. Exposed metallic mounting parts of external
regen resistors must be connected to protective earth and the electrically
conducting parts mechanically shielded for safety. High voltage warning
stickers are also recommended.

Required for

CE-Compliance