Equipment mounting, Ds2100 user's manual (preliminary), 2 equipment mounting – Moog DS2100 User Manual

Page 15

Advertising
background image

SECTION 3: WIRING AND INSTALLATION

DS2100 User's Manual (Preliminary)

PAGE 3-9

3.2 Equipment Mounting

This section details the mechanical dimensions of the DS2100 chassis, as well as required clearances for cabling etc. The
DS2100 is designed to be panel or cabinet mounted. The DS2100 must be mounted in a vertical orientation. The DS2100
must be panel mounted within an enclosure or cabinet that provides a degree of ingress protection against liquids and
objects of at least IP54. Such enclosures or cabinets must be accessible to technically qualified service or maintenance
persons only. It is recommended that the cabinet be ventilated using filtered or conditioned air, free of corrosive or
electrically conductive contaminants. The accumulation of dust, dirt, etc. on the equipment must be avoided. A
minimum clearance above and below each of the DS2100 drive sizes is required. These distances are detailed in Table
3.1.

DS2100 Size

Minimum Clearance Top

(mm)

Minimum Clearance Bottom

(mm)

mA & A

60

100

B

60

100

C

80

160

D

100

200

Table 3.1 Minimum Clearance around DS2100 Drives

If any of the DS2100 units are mounted in a closed cabinet, allow 80mm clearance at the front for cable bends.

Advertising