Central shutdown configuration, Network management cards, User manual – MGE UPS Systems 66074 User Manual

Page 36

Advertising
background image

www.mgeups.com

Network
Management Cards

User Manual

T H E U N I N T E R R U P T I B L E P O W E R P R O V I D E R

Network Management Card

– User Manual

34003676EN/GA

Page

36/69

Z

Remove : Depending on the kind of application, the selected ones will definitively disappear from the table

as SNMP applications, or they will disappear and automatically re-subscribe as the Network Shutdown

Module application.

Z

Utility failure Test : Two alarms 'Utility failure' and 'Utility restored' spaced of 60 seconds will be sent to the

applications selected, making sure that the applications can be reached over the network.

Z

Shutdown Test : This test simulates a UPS on battery operation, it sends alarms to the selected

applications. It enables an easy check to see if the server protection works correctly.- No intervention on

the UPS is required.

- Simulated alarms will be processed by the applications selected only.

- Warning :This test will generate a REAL shutdown sequence of servers on which Network Shutdown

Module is running.

Add NMS allows to add a SNMP trap receiver as a Network Management System.

Modify NMS allows to modify a SNMP trap receiver.

Both buttons makes appear a new window where it is possible to enter the Application name, the

Hostname or IP Address, the Trap community and the severity.

Z

Trap community indicates the name of the SNMP community

For more details, read the MIB description document: 34003627zjaa.pdf , available in the

Embedded

zone of

the

www.mgeups.com

site.

3.5.4 Central Shutdown Configuration

Click the “Notified Application” section in the menu then in “Configuration”.