4.1.1.3 Shutdown when backup time is less than

When the Network Management Card detects that the percentage of backup time remaining is less than the
value set, the shutdown sequence is started.

4.1.1.4 Shutdown duration

Duration required for the systems protected by the Shutdown Modules to shut down (in seconds).

4.1.2 Specific set-up for long autonomy installation (> 30 mn)

On installation where the backup period is longer than 30 minutes, the Network Management Card will initiate
automatically a shutdown at the end of the shutdown timer if this parameter is selected on the “Shutdown
parameters” page.

4.1.3 Controlled outlets

Some UPS models are equipped with outlets (typically 2), that can be controlled individually (while still
remaining dependent on the main UPS control).
Shutdown of the main outlet systematically causes shutdown of the programmable outlets.

Depending on the UPS range, the following notation is used to mark these outlets:

Z

Main outlet:

Main or

1

Z

Programmable outlet 1

1

or

2

Z

Programmable outlet 2

2

or

3

4.1.4 Connecting a server protected by UM-Client to a programmable outlet

Only UM-Client is compatible with the programmable outlets, the Network Shutdown Module will be compatible
with release 3.0.
After connecting the server electrically to one of the controlled outlets, UM-Client must be informed of the outlet
number to which it is connected.
Start UM-Editor (installed with Solution-Pac / WAN), select the “Switchable plug” box and specify the outlet
number (1=main, 2 or 3) in the “Receptacle Number” field.