Connection to the Network Management Card by CAT5 straight RJ45 network cables (maximum

card/sensor distance: 20m)

3.6.2 Environment status

For both measurements, a graduated gauge proposes the following functions:
The cursor indicates the current value.
Two red zones to the left and right represent the high and low thresholds that can be set on the

Environment

Settings

page.

When the measured value enters one of these zones, a alarm can be notified (see Notification parameter in
the

Environment Settings

page).

Time-stamped minimum and maximum temperatures show the extreme values recorded since the last Reset
Min/Max
, a thin dotted line shows their positions on the gauge.
Min and Max can be forced at any time to the current value by clicking on the Reset Min/Max button.
Calibrate: the sensor is calibrated in the factory, but the user can apply an offset to adjust the measurement.
Input # 1 and Input # 2 show the position of the two contacts acquired by the sensor.
The position is displayed with the parameters entered in the

Environment Settings

page.

The last status change of each contact is time-stamped.

The Internet browser updates this page regularly according to the Environment refresh rate parameter on the

System settings

page.