4.2 The different server and UPS shutdown sequences

4.2.1 Extended power outage, shutdown initiated by the Shutdown Timer

During battery backup time, the Shutdown Timer of the Network Management Card is reached: after a user-

defined backup time period, the shutdown of all servers is initiated, followed by the UPS shutdown (depending

on its configuration). The UPS restarts when utility power is restored (depending on its configuration).

Z

Shutdown Duration: Maximum value of shutdown times of the Network Shutdown Modules and UM-

Clients subscribed to the card and depending on the main UPS outlet. This value is updated each time a
client subscribes/ unsubscribes.

Z

Shutdown Duration 1 (2): Maximum value of shutdown times of the UM-Client subscribed to the card and

dependent on outlet 1 (2). This value is updated each time a UM-Client dependent on outlet 1 (2)
subscribes /unsubscribes.

Note: During battery operation, these values are not updated.

4.2.1.1 Main UPS outlet

Shuts down after the ShutDown Timer + Shutdown Duration after having stopped the servers
Restarts when utility power is restored (possibility of programming a restart delay)

Utility

ON

OFF

ON

Trap 17

Trap,11, Trap 29 ShutdownTim

er

Trap 18

Trap 31

Shutdown

Duration

Trap 32

NSM / UMC

Shutdown

Reboot

Main outlet

OFF

4.2.1.2 Programmable outlet 1

Shuts down after Shutoff Delay 1 after having stopped the servers dependent on outlet 1
Restarts when utility power is restored by applying Restart Delay 1

Trap 29

ShutoffDelay 1

Restart

Delay 1

Trap 31

Shutdow

Trap 32

UM-Client

Outlet 1

OFF