HORIZONTAL (THROUGH-THE-WALL)
TERMINATION CONFIGURATION
(Continued)

• If a 90° elbow is used in the horizontal vent run (level height

maintained) the horizontal vent length is reduced by 36"
(914 mm) (Fig. 21 A and B) This does not apply if the 90°
elbows are used to increase or redirect a vertical rise. See
Figure 24.

Example: According to the vent graph (page 17) the
maximum horizontal vent length in a system with a 7.5'
vertical rise is 20’ (6m) and if a 90° elbow is required in
the horizontal vent it must be reduced to 17' (5.2 m).
In Figures 23 and 24,
Dimension A plus B must not be greater
than 17' (5.2m).
• The maximum number of 45° elbows permitted per side

wall installation is two (2). These elbows can be installed
in either the vertical or horizontal run.

• For each 45° elbow installed in the horizontal run, the length

of the horizontal run MUST be reduced by 18" (45cm). This
does not apply if the 45° elbows are installed on the vertical
part of the vent system.

• The maximum number of elbow degrees in a system is 270°.

See Figure 25.

Figure 24 - Maximum Vent Run with Elbows

Example:

Elbow 1 = 90°

Elbow 2 = 45°

Elbow 3 = 45°

Elbow 4 = 90°

Total Angular Variation = 270°

Figure 23 - Horizontal Run Reduction

Figure 25 - Maximum Elbow Usage

VENT INSTALLATION

90°

A + B = 17' Maximum

Horizontal 90° Elbow = 3' Reduction

1 + 2 + 3 + 4 = 270°

1
2
3
4

1
2
3
4

7'6"

A

B

7'6"

10'

7'

A

B