Vent installation, Warning – Monessen Hearth Direct Vent Gas Fireplace MDV500 User Manual

Page 22

Advertising
background image

22

75D2523

10

1

/

2

"

(267mm)

10

1

/

2

"

(267mm)

8

1

/

2

"

(216mm)

Combustible

Wall

Noncombustible

Wall

9

1

/

2

"

(241mm)

9

1

/

2

"

(241mm)

3

3

/

4

"

(92mm)

7

1

/

2

"

(190mm)

VENT INSTALLATION

1. Locate and cut the vent opening in the wall.

For combustible walls first frame in opening.

Combustible Interior Walls:

Cut a 12

1

/

2

"H x

10

1

/

2

" W hole through the interior wall.

Combustible Exterior Walls:

Cut a 10

1

/

2

"H

x 10

1

/

2

"W square hole through the exterior

wall frame. See Figure 17.

Noncombustible Walls:

Hole opening should

be 8

1

/

2

" (216mm) in diameter.

2. The center of the hole should line up with the

center line of the horizontal rigid vent pipe
end. Allow

1

/

4

" minimum rise per foot. See

Figure 26.

Figure 26 - Exterior Wall Framing Dimensions for 5"x8"

WARNING

You may use a reducer from 5"x8"
to 4"x6

5

/

8

" for horizontal with

vertical rise applications. ONLY
use framing instructions below
when using 4"x6

5

/

8

" venting.

If the reducer is installed at the rear
of the unit, you must immediately
follow with a 90° elbow for a
vertical rise before continuing
with any horizontal run. There is
a minimum total height of 7 feet
from the fireplace floor to the last
section of pipe. Refer to graph
on page 17.

1. Locate and cut the vent opening in the wall.

For combustible walls first frame in opening.

Combustible Interior Walls:

Cut a 11

1

/

2

"H x

9

1

/

2

" W hole through the interior wall.

Combustible Exterior Walls:

Cut a 9

1

/

2

"H

x 9

1

/

2

"W square hole through the exterior

wall frame. See Figure 16.

Noncombustible Walls:

Hole opening should

be 7

1

/

2

" (190mm) in diameter.

2. The center of the hole should line up with the

center line of the horizontal rigid vent pipe
end. Allow

1

/

4

" minimum rise per foot. See

Figure 27.

Figure 27 - Exterior Wall Framing Dimensions

for 4"x6

5

/

8

"

HORIZONTAL WITH VERTICAL RISE (THROUGH-THE-WALL) APPLICATIONS

NOTE: #1222DA reducer must be used when 4x6

5

/

8

" venting

is preferred. Reducer must be installed directly onto
unit at pipe adaptor before vertical rise.

Advertising