Microstepping MForce PowerDrive Manual Revision R040507

WARNING! DO

NOT connect

or disconnect

power leads

when power is applied!

Disconnect the AC power

side to power down the

DC power supply.

Example C – Cabling 50 Feet or Greater, AC Power to Power Supply

Figure 2.2.4: AC To Full Wave Bridge Rectifier, Cabling over 50 Feet

Figure 2.2.5: AC Cabling - 50 Feet or Greater - AC To Power Supply

Shield to Earth Ground

on Supply End Only

P

Type RFI Filter

r Required Current

Transformer - 10 to 28 VAC RMS for 48 VDC Systems

20 to 48 VAC RMS for 75 VDC Systems

Full Wave Bridge

+

-

Shielded Twisted Pair

Cable Length

as required

NOTE:

Connect the cable illustrated

in Figure 2.2.2 to the output of

the Full Wave Bridge

Example B: AC Power to Full Wave Bridge Cabling Over 50 Feet

Shield to Earth Ground

on Supply End Only

P

Type RFI Filter

r Required Current

120 or 240 VAC

Dependent on

Power Supply

Power Supply

+

-

DC Volts Out

Shielded Twisted Pair

Cable Length

as required

NOTE:

Connect the cable illustrated

in Example A to the output of

the Power Supply

MForce PowerDrive Recommended Power Supply Cable AWG

1 Amperes (Peak)

3 Amperes (Peak)

Length (Feet)

10

25

50*

75* 100*

Length (Feet)

10

25

50*

75*

100*

Minimum AWG

20

20

18

18

16

Minimum AWG

18

16

14

12

12

2 Amperes (Peak)

4 Amperes (Peak)

Length (Feet)

10

25

50*

75* 100*

Length (Feet)

10

25

50*

75*

100*

Minimum AWG

20

18

16

14

14

Minimum AWG

18

16

14

12

12

*Use the alternative methods illustrated in examples B and C when cable length is ≥ 50 feet. Also, use the same

current rating when the alternate AC power is used.

Table 2.2.1: Recommended Wire Gauges