17

Part 2: Interfacing and Configuring

Shield to Earth Ground

on Supply End Only

Ferrite Beads

*L z 0.5 MH

* 0.5 MH is a typical starting point for the Common Mode Line Filters. By increasing or decreasing

the value of L you can set the drain current to a minimum to meet your application’s requirements.

Common Mode

Line Filters (2x)

From MicroLYNX

Shielded/Twisted Pair

Cable Length

as required

Motor

Connections

A
A
B
B

A

A

B

B

MForce

PowerDrive

Phase Outputs

Example B: Motor Cabling Greater Than 50 Feet

Figure 2.3.8: Motor Cableing Greater than 50 Feet

Recommended Motor Cable AWG Sizes

MForce PowerDrive Recommended Motor Cable AWG

1 Amperes (Peak)

5 Amperes (Peak)

Length (Feet)

10

25

50*

75* 100*

Length (Feet)

10

25

50*

75*

100*

Minimum AWG

20

20

18

18

16

Minimum AWG

16

16

14

12

12

2 Amperes (Peak)

6 Amperes (Peak)

Length (Feet)

10

25

50*

75* 100*

Length (Feet)

10

25

50*

75*

100*

Minimum AWG

20

18

16

14

14

Minimum AWG

14

14

14

12

12

3 Amperes (Peak)

7 Amperes (Peak)

Length (Feet)

10

25

50*

75* 100*

Length (Feet)

10

25

50*

75*

100*

Minimum AWG

18

16

14

12

12

Minimum AWG

12

12

12

12

12

4 Amperes (Peak)

*Use the alternative methods illustrated in example

B when cable length is ≥ 50 feet. Also, use the same

current rating when the alternate AC power is used.

Length (Feet)

10

25

50*

75* 100*

Minimum AWG

18

16

14

12

12

Table 2.3.1: Recommended Wire Gauges