Page: 104

8.7.5 OUTPUT EXPANSION PANEL TESTING

The relay outputs can be forced to the energized state by
using the front panel

TEST ALARMS

function.

The analog outputs can be forced to 4 mA by using
diagnostic code 0012.

The analog outputs can be forced to 20 mA by using
diagnostic code 0013.

The analog outputs can be returned to normal operation
by using diagnostic code 0000.

8.7.6 INDIVIDUAL RELAY SPECIFICATIONS

Dimensions

7.0” X 4.2” X 1.2” (HWD)

Relays

Number of Relays

16 SPDT

Contact Rating

6A

Wire Terminals

Screw Terminals

Analog Outputs

Number of Outputs

8

Scale

4-20 mA

Loop Resistance (max.)

800 Ohms

Wire Terminals