APPENDIX A - SPECIFICATIONS

Page: 85

8.1 APPENDIX A - SPECIFICATIONS

A. OPERATING

OPERATING TEMPERATURE

Controller

32 to 122oF (0 to 50oC)

STORAGE TEMPERATURE

Controller:

-40 to 130oF (-40 to 55oC)

HUMIDITY

Controller:

10% to 95% RH

POWER

Standard

120 VAC +10%/-15%, 60 Hz

12 VDC Nom; 10 to 29 VDC

Optional

220 VAC +10%/-15%, 50 Hz

12 VDC Nom; 10 to 29 VDC

Consumption

48 Watts max. (eight modules)

RELAYS

Three DPDT 3A, 115 VAC (Low, High, Trouble)

Sixteen SPDT 6A, 115 VAC (Model 5392-00)

Sixteen SPDT 6A, 115 VAC (Model 4314-01)

ANALOG OUTPUTS

Eight 4-20 mA, channel value (Model 4314-01)

Loop Resistance max. 800 Ohms

NUMBER OF CHANNELS

5000-02: Two channels, upgradeable to four or eight

5000-04: Four channels, upgradeable to eight

5000-08: Eight channels

PRINTER INTERFACE

Standard on 5000-08, option on -02 & -04

RS232 Port

1200 Baud

8 bits, no parity

1 start bit, 2 stop bits

MODBUS INTERFACE (Replaces printer interface)

Optional MODBUS communication protocol

Honeywell Multivendor Approved for TDC 3000 Gateway

COMPONENTS

Microprocessor

Z84 (4 MHz - 8 bit CPU)

Memory

64K bytes EPROM

8K bytes Static RAM

(battery backed-up)

Displays

4 digit 1/2” LCD

32 character (2X16) dot matrix

alphanumeric LCD

11 LED indicators

Battery

Hi energy lithium

3 year retention

Keypad

7 key sealed membrane

Power Supply

Integral High efficiency AC/DC with
line filter

TRANSMISSION

Digital, pulse width modulated - RFI, EMI immune

B. PHYSICAL

DIMENSIONS

Controller

Rack Mount

7" X 4.5" X 12" (H W D)
17.5cm X 11.25cm X 30cm

NEMA 4X Enclosure

17.5" X 16.2" X 6.35" (H W D)
44.5cm X 41.1cm X 16cm

NEMA 7 Enclosure

22.0" X 21.5" X 14" (H W D)
55.9cm X 54.6cm X 35.6cm

Module Housing

Environment

NEMA 7 (NEMA 4X Optional)

5100-01, 5100-02

7.5" X 4" X 4" (H W D)

19cm X 10cm X 10cm

5100-03

8.5" X 4" X 4" (H W D)

19cm X 10cm X 10cm

5100-04 : -24, -27

7.5" X 4" X 4" (H W D)

19cm X 10cm X 10cm

5100-25

10" X 4" X 4" (H W D)

19cm X 10cm X 10cm

WEIGHT

Controller

Rack Mount

7 pounds (3.2 kg)

NEMA 4X Enclosure

25 pounds (11.3 kg)

NEMA 7 Enclosure

143 pounds (65.0 kg)

Module

2 pounds (0.9 kg)

MOUNTING

Controller

Instrument Rack
Chassis Mount Panel
Wall Mount Bracket
NEMA 4X Enclosure
NEMA 7 Enclosure

Module

Conduit or flexible cable

MODULE CABLE

Typical: three conductor 18 AWG,

See installation instructions for alternative wire sizes

SENSOR TYPES

Hydrogen Sulfide

Thin film, solid state (5100-01)

Combustible

Catalytically bead (5100-02)

Oxygen

Electrochemical (5100-03).

Carbon Monoxide (CO) Electrochemical (5100-04)

Hydrogen Sulfide

Electrochemical (5100-05)

Chlorine

Electrochemical (5100-06)

Hydrogen

Electrochemical (5100-07)

Sulfur Dioxide

Electrochemical (5100-10)

Nitrogen Dioxide

Electrochemical (5100-12)

CO High Range

Electrochemical (5100-13)

CO -

Hydrogen Tolerant

Electrochemical (5100-16)

Nitric Oxide

electrochemical (5100-19)

Hydrogen Chloride

Electrochemical (5100-21)

Hydrogen Cyanide

Electrochemical (5100-22)

Ammonia

Electrochemical.(5100-25)

Ethylene Oxide

Electrochemical (5100-27)