CONFIGURATION PROCEDURE

Page: 35

4.3 CONFIGURATION INSTRUCTIONS

Sentry controllers which are components of complete systems
are factory configured and generally do not require changes
prior to being placed in service.

Sentry controllers which have not been factory configured can
be placed into operation with default values for all configuration
parameters by using the diagnostic code “0021” described in
Section 8.3 of this manual.

The following are step-by-step configuration instructions which
can be used to customize the operation of the controller for
specific applications. After initial configuration the controller
can be placed in service or used for training as described in the
this section.

If an error is made, or suspected, press the RESET key until the
display reads <RESET SYSTEM> and then press the ENTER
key, the system will reset and the set-up routine can be re-
started.

STEP

KEY

LOWER DISPLAY

1

RESET

<RESET ALARMS>

2

RESET

<RESET SYSTEM>

3

ENTER

SYSTEM RESET COMPLETE

<UNCALIBRATED>

Displays continue cycling through each
module number. Power light changes from
flashing to solid.

4

MODE

<CALIB/CHANGE>

5

ENTER

CHANGE MODE SELECTED

Note that if a user entry code has been

initiated it must be input here.

Change/Calibrate light turns on.

READ INSTRUCTION MANUAL FIRST

PRESS ENTER TO CALIB ALL [GGGG]

Where GGGG is the gas type.

6

MODE

<CHANGE CALIB>

7

MODE

<CHANGE MODULE>

8

ENTER

USE ARROWS/ENTER

MODULE # = 1

9

ENTER

GAS TYPE : GGGG

10

ENTER

# 1 GGGG IS: ON

11

ENTER

LO ALM: NONLATCH

Use arrows to change.

12

ENTER

HI ALM: LATCH

Use arrows to change.

13

ENTER

HIGH ALARM = XX

Use arrows to change each digit.

14

ENTER

LOW ALARM = XX

Use arrows to change each digit.

STEP

KEY

LOWER DISPLAY

15

ENTER

FACTOR = 100

Linearizing factors are required for sensor

modules 5100-01 (H

2

S) .

Scaling factors can be used for sensor

module 5100-02 (Combustibles)

16

ENTER

MODULE # = 2

Repeat steps 9 through 15 for each module.

17

MODE

<SET USER CODE>

18

MODE

<CHANGE PRINTER>

or

<CHANGE MODBUS>

Displays only if printer or MODBUS

option is installed.

19

MODE

CHANGE GAS TAG

20

MODE

CHANGE MOD TAG

21

MODE

CHANGE ENG UNITS

22

MODE

<OPERATE MODE>

23

ENTER

OPERATE MODE SELECTED

24

TIME

<CHECK HISTORY>

25

TIME

<HISTORY REPORT>

For printer option only.

26

TIME

<SYSTEM REPORT>

For printer option only.

27

TIME

<STATUS REPORT>

For printer option only.

28

TIME

<SET DATE & TIME>

29

ENTER

D&T MM/DD HH:MM

Set each digit using the arrows, then
ENTER to advance to the next digit.

28

RESET

H2S PPM

Display will scan through all active gas

sensor modules.

4.4 SENTRY TRAINING

After the controller is configured use this section in conjunction
with the Sentry

MENU,

Table

4-2, and Sentry

FLOWCHARTS, Figure 4-3 through Figure 4-7 to develop an
understanding of keyboard operation.

To begin, press the RESET key until the lower display reads
PRESS ENTER TO RESET SYSTEM then press ENTER.
The system is now in "normal operate mode". The Sensor/Level
display will cycle through each of the module numbers
(CONTINUOUS SCAN). If any module is indicated as
MODULE OFF use steps 9 through 15 of Section 4.3 to turn
that module ON.