Sentry Industries 5000 User Manual

Page 59

Advertising
background image

SMC

sierra monitor corporation

Sentry Instruction Manual - Version 6

MAINTENANCE

Page: 53

6. MAINTENANCE

6.1 MAINTENANCE REQUIREMENTS

The following are the manufacturer’s recommendations
for periodic maintenance of the Sentry system:

1

CALIBRATION

: All sensors should be calibrated at a

minimum of every 90 days.

NOTE

FMRC approved combustible gas sensors are required to

be calibrated every 90 days.

2

BATTERY REPLACEMENT

: The lithium battery for

memory retention should be replaced every two
years. (See Service)

3

DUST AND DIRT CONTROL

: When calibration is

performed the controller and the modules should be
checked visually to determine if dust or dirt build up
needs to be removed. This cleaning should be done
with dry instruments such as compressed air, cloth
wipes or whisk broom.

4

WIRING OR CABLE CONDITIONS

: Any wiring or

cables which are not conduited should be checked
once a year for damage to insulation or corrosion of
splice or terminal points.

5

LUBRICATION

: Lubricate metal to metal parts

(module lid) periodically.

6

INSPECTION

: Inspect modules, periodically, for

moisture or water accumulation.