Sentry Industries 5000 User Manual

Page 2

Advertising
background image

SMC

sierra monitor corporation

Sentry Instruction Manual - Version 6

FMRC APPROVAL

ONLY THE FOLLOWING ITEMS, FUNCTIONS AND OPTIONS ARE FMRC* APPROVED

Sentry Model 5000 Gas Monitoring System

Controllers

Model 5000-02

Two Channel Controller

Model 5000-04

Four Channel Controller

Model 5000-08

Eight Channel Controller

Controller Options:

Model 5380-00

Rack Mount Configuration

Model 5383-00

NEMA-4X Configuration

Model 5387-00

Printer Output Software

Model 5392-00

Individual Alarm Relays

Sensor Module

Model 5100-02

Combustible Gas Sensor Module

Model 5100-05

Hydrogen Sulfide Sensor Module - EC Cell

Calibration Equipment

Model 1200-26

Calibration Gas Delivery System

Model 1290-02

Combustible Gas Cylinder

Model 5358-00

Calibration Head, Magnetic

Model 5358-01

Calibration Head, Standard

Model 5360-00

Calibration Gas Delivery Fitting

Notes:

1)

FMRC Approval applies only to conventional (one cable run per sensor module) or
multiplexed (multiple sensor modules per cable) installations. Apparatus must be
installed in accordance with National Electrical Code.

2)

FMRC Approval of the RS232C Data Output option applies only if used as a printer
port and the apparatus connected to the controller does not use or generate greater
than 250 Vrms.

3)

FMRC Approval for Hydrogen Sulfide Sensor Module applies to Model 5100-05
electrochemical cell only. Model 5100-01 solid state sensor is not approved.

4)

FMRC Approval allows the presence of MODBUS firmware in the Sentry controller
but does not cover the operation of the MODBUS firmware itself.

*FMRC: Factory Mutual Research Corporation