SERVICE

Page: 55

7. SERVICE

7.1 OVERVIEW

7.1.1 GENERAL

This section provides service information for Sentry
systems which have software version 6.0 and above The
section is intended for use by a qualified field technician.
Sierra Monitor sales and technical staff are available to
assist by telephone at (408) 262-6611, during normal west
coast working hours.

7.1.2 INSTALLATION INSPECTION

Prior to system start-up or trouble shooting the entire
system should be visually inspected. The following are
guidelines for that inspection:

7.1.2.1 CONTROLLER INSTALLATION

Controller installed in conformance to
instruction manual recommendations.

AC power is correctly grounded.

Hot AC and relay connections have safety
covers installed.

RS232C cable connection to printer correctly
seated and retaining screws tight.

7.1.2.2 CABLING INSTALLATION

All splices are soldered or via terminal block.

Cabling is away from sources of electrical noise
where possible.

Terminals P, S, G (or 1,2,3) on channel
connector match terminals P, S, G on module.
Trace color codes to confirm correct wiring.

7.1.2.3 SENSOR MODULE INSTALLATION

Module installation in conformance with
instruction manual recommendations.

Modules accessible for calibration.

Terminations to electronics card clean and
correct.

7.1.2.4 MOISTURE TRAPS AND RAINSHIELDS

Conduit seals and drains installed to avoid
moisture build up in electronics enclosure.
Water accumulation in sensor module
enclosures is a major cause of damage and
system failures - take precautions to seal

electrical conduits and provide moisture traps
and drains to avoid water damage

Rainshields installed where applicable.

7.1.2.5 STANDARD VOLTAGES

AC Voltage on AC terminal on connector panel
of controller should be 120 VAC (or 220 VAC
option) +10%, -15%, 50-60 Hz.

DC Voltage on DC terminal on connector panel
(if used) should be (12 VDC Nominal), 10 to 29
VDC.

Channel Voltage (power to ground) should be
approximately 20 VDC on open channel and
approx. 18 VDC on used channel.

Signal Oscillation on an “in use” channel (signal
to ground) can usually be read with a voltmeter
at approx. 0 - 6 VDC.

7.1.3 DATA COLLECTION

Sentry can provide a large amount of data which will be
helpful during problem solving. If the system has a
printer use the

TIME

KEY

to select

HISTORY

REPORT

and

press

ENTER

. When the report is complete

SYSTEM

REPORT

will display on the controller, press

ENTER

to

print. Diagnostic reporting capability is discussed in
Section 7.3.5.

If a printer is not in use, key information can be read and
manually recorded by selection of the

HISTORY

(TIME

KEY),

CHECK

MODULE

and

CHECK

SYSTEM

(MODE

KEY)

menu choices

7.1.4 INSPECTION AND TROUBLESHOOTING GUIDE

The inspection and troubleshooting guide can be used to
step through the system start-up and to determine the
corrective action if a fault occurs.

Instructions:

1. Take the action described in the "Operator

Action" column.

2. If the “CORRECT” result occurs, proceed to the

next Operator Action.

3. If the “Incorrect” result occurs find the probable

cause and corrective action in the “Reason/
Correction” column.