SERVICE

Page: 63

7.3 COMMUNICATIONS

7.3.1 DESCRIPTION OF COMMUNICATIONS

The Sentry controller scans each channel in turn taking
less than one second to scan all channels. At each
channel:

1. A "reset" signal is sent out to clear all module

communications.

2. An address (which is a module number) is sent

out and the controller waits for a response. The
response is a digital frequency which is
proportional to the first of eight parameters
which are interrogated by the controller.

3. Because the controller received an answer and

knows that the particular module is on that
channel it continues to interrogate that module
to retrieve the remaining seven parameters
before moving to the next module number.

The eight (total) signals are:

Value of Ground.

Value of sensor signal (relates to gas
concentration).

Heater voltage (Type 1 Module) or
Bridge Voltage (Type 2 Module).

Heater current (Type 1 Module) or
Bridge Current (Type 2 Module).

Sensor type (Type 1 through 4
Modules).

Calibration switch condition on/off.

Module voltage (tests line drop from
controller to module).

Reference voltage (used together
with ground to ratiometrically
compensate for any temperature drift
in module components)

The controller interprets the information received during
the polling and takes actions as necessary. (Any deviation
from normal is rapidly validated to avoid errors due to
electrical noise.) The information, combined with
continual system diagnostics allows the controller to
accurately determine abnormal conditions. Table 7-1
provides a categorized listing of Sentry messages.

SYSTEM ERRORS

MODULE ERRORS

WARNING/STATUS MESSAGES

E-01 (ROM Check Failed)

DISCONNECTED

NO MODULE

E-02 (RAM Check Failed)

CHECK POWER ADJ

MODULE OFF

TIMER FAILURE

MODULE VOLTAGE LOW

WARM-UP WAIT - 00:00

CLOCK FAILURE

SENSOR FAILURE

FACTOR MISSING

DUPLICATE MODULE

UNCALIBRATED

CHK BRIDGE VOLTAGE

REPLACE SENSOR

TYPE ERROR

CALIBRATION OVERDUE

REPLACE BATTERY

CALIBRATION SWITCH ON

DIAGNOSTIC SCAN

FAST ERROR CHECK

LOW SENSITIVITY

NOT CALIBRATED

CALIBRATION ABORTED

Table 7-1

Sentry Error and Diagnostic Messages