Ratings for Input Line Currents, Type H Constant Torque 208/230 Vac
Single-Phase Input with Three-Phase Output, Switching Frequency at 4 kHz
Drive Controller
Catalog Number
Motor Power
208/230 Vac
Rated
Output
Current
In
Input Line Current
2000 AIC
5000 AIC
22000 AIC
w/ Additional 3%
Line Impedance
22000 AIC
kW
HP
A
208 V
A
230 V
A
208 V
A
230 V
A
208 V
A
230 V
A
208 V
A
230 V
A
ATV58HU09M2•
0.37
0.5
2.3
5.6
4.7
—
—
—
—
4.2
3.8
ATV58HU18M2•
0.75
1
4.1
9.8
8.3
—
—
—
—
7.9
7
ATV58HU29M2•
1.5
2
7.8
—
—
18.5
15.6
—
—
14.1
12.3
ATV58HU41M2•
2.2
3
11
—
—
25.6
21.6
—
—
20.5
17.5
ATV58HU72M2•
3
4
13.7
—
—
25.1
22.7
—
—
23.3
20.6
ATV58HU90M2•
4
5
18.2
—
—
27.5
24.8
30.7
27.6
32.3
28.6
ATV58HD12M2•
5.5
7.5
24.2
—
—
39.8
36.6
44.9
40
42.5
37.6
Ratings for Input Line Currents, Type H Variable Torque Low Noise 208/230 Vac
Single-Phase Input with Three-Phase Output,
Switching Frequency: ATV58HU09M2 to D12M2 at 8kHz, ATV58HD16M2 to D46M2 at 4 kHz
Drive Controller
Catalog Number
Motor Power
208/230 Vac
Rated
Output
Current
In
Input Line Current
2000 AIC
5000 AIC
22000 AIC
w/ Additional 3%
Line Impedance
22000 AIC
kW
HP
A
208 V
A
230 V
A
208 V
A
230 V
A
208 V
A
230 V
A
208 V
A
230 V
A
ATV58HU09M2•
0.37
0.5
2.3
5.6
4.7
—
—
—
—
4.2
3.8
ATV58HU18M2•
0.75
1
4.8
9.8
8.3
—
—
—
—
7.9
7
ATV58HU29M2•
1.5
2
7.8
—
—
18.5
15.6
—
—
14.1
12.3
ATV58HU41M2•
2.2
3
11
—
—
25.6
21.6
—
—
20.5
17.5
ATV58HU72M2•
3
4
14.3
—
—
25.1
22.7
—
—
23.3
20.6
ATV58HU90M2•
4
5
17.5
—
—
27.5
24.8
35
30
32.3
28.6
ATV58HD12M2•
5.5
7.5
25.3
—
—
39.8
36.6
46
39.4
42.5
37.6
ATV58HD16M2•
[1]
7.5
10
30.8
—
—
—
—
—
—
60
53
ATV58HD23M2•
[1]
11
15
46.2
—
—
—
—
—
—
86
76
ATV58HD28M2•
[1]
15
20
60
—
—
—
—
—
—
115
102
ATV58HD33M2•
[1]
18.5
25
75
—
—
—
—
—
—
141
125
ATV58HD46M2•
[1]
22
30
88
—
—
—
—
—
—
168
149
[1]
A 3% line reactor must be used when supplied with single phase input.
Ratings for Input Line Currents, Type H Constant Torque 208/230 Vac
Three-Phase Input with Three-Phase Output
Switching Frequency: ATV58HU29M2 to D23M2 at 4kHz, ATV58HD28M2 to D46M2 at 2 kHz
Drive Controller
Catalog Number
Motor Power
208/230 Vac
Rated
Output
Current
In
Input Line Current
5000 AIC
10000 AIC
22000 AIC
w/ Additional 3%
Line Impedance
22000 AIC
kW
HP
A
208 V
A
230 V
A
208 V
A
230 V
A
208 V
A
230 V
A
208 V
A
230 V
A
ATV58HU29M2•
1.5
2
7.8
9.7
8.3
—
—
—
—
6.6
5.9
ATV58HU41M2•
2.2
3
11
13.4
11.4
—
—
—
—
9.5
8.5
ATV58HU54M2•
3
4
13.7
17.2
15
—
—
—
—
12.6
11.2
ATV58HU72M2•
4
5
18.2
22.4
19.5
—
—
—
—
16.9
14.6
ATV58HU90M2•
5.5
7.5
24.2
30
26.4
32.1
28.4
34.7
30
23.3
20.6
ATV58HD12M2•
7.5
10
31
39.7
35
42.3
37.4
44.4
38.2
32.3
28.6
ATV58HD16M2•
11
15
47
42.4
43.1
42.8
43.3
43.4
43.6
43.4
43
ATV58HD23M2•
15
20
60
58
58.5
58.2
58.3
58.5
58.7
58.5
58.7
ATV58HD28M2•
18.5
25
75
70.2
70.4
70.6
70.4
70.2
70.4
69.4
70
ATV58HD33M2•
22
30
88
82.3
82.7
82.5
83.9
84
84
83.2
83.6
ATV58HD46M2•
30
40
116
100.8
102.2
101.2
103.2
101.7
101.5
101.7
103.7
NOTE: The input
conductor ampacity
rating should not be
less than the
ampacity rating
selected based on the
rated controller output
current.