Ratings for Input Line Currents, Type H Constant Torque 208/230 Vac
Single-Phase Input with Three-Phase Output, Switching Frequency at 4 kHz

Drive Controller

Catalog Number

Motor Power

208/230 Vac

Rated

Output

Current

In

Input Line Current

2000 AIC

5000 AIC

22000 AIC

w/ Additional 3%

Line Impedance

22000 AIC

kW

HP

A

208 V

A

230 V

A

208 V

A

230 V

A

208 V

A

230 V

A

208 V

A

230 V

A

ATV58HU09M2•

0.37

0.5

2.3

5.6

4.7

4.2

3.8

ATV58HU18M2•

0.75

1

4.1

9.8

8.3

7.9

7

ATV58HU29M2•

1.5

2

7.8

18.5

15.6

14.1

12.3

ATV58HU41M2•

2.2

3

11

25.6

21.6

20.5

17.5

ATV58HU72M2•

3

4

13.7

25.1

22.7

23.3

20.6

ATV58HU90M2•

4

5

18.2

27.5

24.8

30.7

27.6

32.3

28.6

ATV58HD12M2•

5.5

7.5

24.2

39.8

36.6

44.9

40

42.5

37.6

Ratings for Input Line Currents, Type H Variable Torque Low Noise 208/230 Vac
Single-Phase Input with Three-Phase Output,
Switching Frequency: ATV58HU09M2 to D12M2 at 8kHz, ATV58HD16M2 to D46M2 at 4 kHz

Drive Controller

Catalog Number

Motor Power

208/230 Vac

Rated

Output

Current

In

Input Line Current

2000 AIC

5000 AIC

22000 AIC

w/ Additional 3%

Line Impedance

22000 AIC

kW

HP

A

208 V

A

230 V

A

208 V

A

230 V

A

208 V

A

230 V

A

208 V

A

230 V

A

ATV58HU09M2•

0.37

0.5

2.3

5.6

4.7

4.2

3.8

ATV58HU18M2•

0.75

1

4.8

9.8

8.3

7.9

7

ATV58HU29M2•

1.5

2

7.8

18.5

15.6

14.1

12.3

ATV58HU41M2•

2.2

3

11

25.6

21.6

20.5

17.5

ATV58HU72M2•

3

4

14.3

25.1

22.7

23.3

20.6

ATV58HU90M2•

4

5

17.5

27.5

24.8

35

30

32.3

28.6

ATV58HD12M2•

5.5

7.5

25.3

39.8

36.6

46

39.4

42.5

37.6

ATV58HD16M2•

[1]

7.5

10

30.8

60

53

ATV58HD23M2•

[1]

11

15

46.2

86

76

ATV58HD28M2•

[1]

15

20

60

115

102

ATV58HD33M2•

[1]

18.5

25

75

141

125

ATV58HD46M2•

[1]

22

30

88

168

149

[1]

A 3% line reactor must be used when supplied with single phase input.

Ratings for Input Line Currents, Type H Constant Torque 208/230 Vac
Three-Phase Input with Three-Phase Output
Switching Frequency: ATV58HU29M2 to D23M2 at 4kHz, ATV58HD28M2 to D46M2 at 2 kHz

Drive Controller

Catalog Number

Motor Power

208/230 Vac

Rated

Output

Current

In

Input Line Current

5000 AIC

10000 AIC

22000 AIC

w/ Additional 3%

Line Impedance

22000 AIC

kW

HP

A

208 V

A

230 V

A

208 V

A

230 V

A

208 V

A

230 V

A

208 V

A

230 V

A

ATV58HU29M2•

1.5

2

7.8

9.7

8.3

6.6

5.9

ATV58HU41M2•

2.2

3

11

13.4

11.4

9.5

8.5

ATV58HU54M2•

3

4

13.7

17.2

15

12.6

11.2

ATV58HU72M2•

4

5

18.2

22.4

19.5

16.9

14.6

ATV58HU90M2•

5.5

7.5

24.2

30

26.4

32.1

28.4

34.7

30

23.3

20.6

ATV58HD12M2•

7.5

10

31

39.7

35

42.3

37.4

44.4

38.2

32.3

28.6

ATV58HD16M2•

11

15

47

42.4

43.1

42.8

43.3

43.4

43.6

43.4

43

ATV58HD23M2•

15

20

60

58

58.5

58.2

58.3

58.5

58.7

58.5

58.7

ATV58HD28M2•

18.5

25

75

70.2

70.4

70.6

70.4

70.2

70.4

69.4

70

ATV58HD33M2•

22

30

88

82.3

82.7

82.5

83.9

84

84

83.2

83.6

ATV58HD46M2•

30

40

116

100.8

102.2

101.2

103.2

101.7

101.5

101.7

103.7

NOTE: The input
conductor ampacity
rating should not be
less than the
ampacity rating
selected based on the
rated controller output
current.

Advertising
This manual is related to the following products: