Altivar, 58 trx ac drives, Communication parameters – Schneider Electric ALTIVAR 58 TRX User Manual

Page 83: Adjustment registers (continued)

Advertising
background image

Altivar

®

58 TRX AC Drives

Communication Parameters

83

09/2003

©

2000–2003 Schneider Electric All Rights Reserved

W262
or 16#5FE5/D

JOG

0.1 Hz

Jog frequency

0 to 100 (0.0 to 10.0 Hz)

W263
or 16#5FE5/E

JGT

0.1 s

Delay between two consecutive jog operations

0 to 20 (0.0 to 2.0 s)

W264
or 16#5FE5/F

SP2

0.1 Hz

Preset speed 2

LSP to HSP

W265
or 16#5FE5/10

SP3

0.1 Hz

Preset speed 3

LSP to HSP

W266
or 16#5FE5/11

SP4

0.1 Hz

Preset speed 4

LSP to HSP

W267
or 16#5FE5/12

SP5

0.1 Hz

Preset speed 5

LSP to HSP

W268
or 16#5FE5/13

SP6

0.1 Hz

Preset speed 6

LSP to HSP

W269
or 16#5FE5/14

SP7

0.1 Hz

Preset speed 7

LSP to HSP

W270
or
16#5FE5/15

IDC

0.1 A

DC injection current level

0.1 to 1.36
x INV (drive controller nominal current)

W271
or 16#5FE5/16

TDC

0.1 s

DC injection time (in the case of automatic DC
injection at stop)
Type FVC: Zero speed holding time with CTR =
closed loop

0 to 300 = 0.0 s to 30.0 s
301 = CONT: continuous injection

W272
or 16#5FE5/17

TLS

0.1 s

Low speed (LSP) dwell timer

0 = No: no limit
1 to 9999 = time of 0.1 s to 999.9 s

W273

[1]

or 16#5FE5/18

BRL

0.1 Hz

Mechanical brake release threshold

0 to 100 (0.0 to 10.0 Hz)

W274
or 16#5FE5/19

BEN

0.1 Hz

Mechanical brake engage threshold
Type FVC: Not significant if
CTR = closed loop

0 to LSP

W275
or 16#5FE5/1A

BRT

0.01 s

Mechanical brake release time

0 to 500 (0.00 to 5.00 s)

W276
or 16#5FE5/1B

BET

0.01 s

Mechanical brake engage time

0 to 500 (0.00 to 5.00 s)

W277
or 16#5FE5/1C

IBR

0.1 A

Mechanical brake release current threshold

0 to 1.36
x INV (drive controller nominal current)

W278
or 16#5FE5/1D

TL2

1%

Second torque limit

0 to 200

W279
or 16#5FE5/1E

RPG

0.01

PI proportional gain

1 to 10000 (0.01 to 100.00)

W280
or 16#5FE5/1F

RIG

0.01/s

PI integral gain

1 to 10000 (0.01 to 100.00)

W281

[1]

or 16#5FE5/20

FBS

0.1

PI feedback scale factor

10 to 1000 (1.0 to 100.0)

W282
or 16#5FE5/21

CTD

0.1 A

Motor current threshold for signalling

0.25 to 1.36 x INV
(INV = drive controller nominal current)

W283
or 16#5FE5/22

TTD

1%

Thermal threshold for signalling

0 to 118

W284
or 16#5FE5/23

FTD

0.1 Hz

Frequency threshold for signalling

LSP to HSP

W285
or 16#5FE5/24

DTS

0.01

Tachogenerator feedback scaling (For I/O card
with analog input)

100 to 200 (1.00 to 2.00)

W286
or 16#5FE5/25

JPF

0.1 Hz

Skip frequency
(frequency range: ±2.5 Hz)

0 to HSP

W287
or 16#5FE5/26

PIC

Inverts the PI feedback signal

0 = No (normal)
1 = Yes (inverted)

W288
16#5FE5/27

SDC

0.1 A

Continuous DC injection braking current level on
stopping after 30 s. See TDC (W271)

Min: 0.1 x INV
Max: 1.36 x INV
(INV = drive controller nominal current)

W289
or 16#5FE5/28

USC

0.01

Machine coefficient. Applied to RFR for custom
display of machine speed under Display parameter
USP (USP = RFR x USC).

1 to 10000 (0.01 to 100.00)

W290
or 16#5FE5/29

BIP

Brake release pulse

0 = No: Pulse in the direction requested
1 = Yes: Always pulse in the ascending direction

W291
or 16#5FE5/2A

INR

Fine increment in the ramp settings for ACC, DEC,
AC2, and DE2

0 = 0.1 s
1 = 0.01 s

W292
or 16#5FE5/2B

SRP

1%

Range of action around the reference for +/–
speed function

0 to 50% of the reference

W293
or 16#5FE5/2C

TA1

1%

Rounding of the start of the acceleration ramp

0 to 100% of ramp time

Adjustment Registers (Continued)

Word

Code

Units

Description

Possible Values or Range

[1]

This parameter does not exist for ATV58 Type FVC drive controllers.