Altivar, 58 trx ac drives, Communication parameters – Schneider Electric ALTIVAR 58 TRX User Manual

Page 91: Special drivecom registers (continued)

Advertising
background image

Altivar

®

58 TRX AC Drives

Communication Parameters

91

09/2003

©

2000–2003 Schneider Electric All Rights Reserved

W610
or 16#6048/1

SPAL

1 rpm

SpdAcc
Acceleration ramp determined by a speed
variation in rpm via words W610 and W611
(32 bits) plus a time variation in seconds
given by word W612 (16 bits)
Read/Write

1 to 65535

W611

SPAH

Reserved

0

W612
or 16#6048/2

SPAT

1 s

SpdAcc
Acceleration ramp determined by a speed
variation in rpm via words W610 and W611
(32 bits) plus a time variation in seconds
given by word W612 (16 bits)
Read/Write

0 to 65535

W613
or 16#6049/1

SPDL

1 rpm

SpdDec
Deceleration ramp determined by a speed
variation in rpm via words W613 and W614
(32 bits) plus a time variation in seconds
given by word W615 (16 bits)
Read/Write

1 to 65535

W614

SPDH

Reserved

0

W615
or 16#6049/2

SPDT

1 s

SpdDec
Deceleration ramp determined by a speed
variation in rpm via words W613 and W614
(32 bits) plus a time variation in seconds
given by word W615 (16 bits)
Read/Write

0 to 65535

Special DRIVECOM Registers (Continued)

Word

Code

Units

Parameter Name and Description

Possible Values or Range