Altivar

®

58 TRX AC Drives

Wiring Recommendations

103

09/2003

©

2000–2003 Schneider Electric All Rights Reserved

Ratings for Input Line Currents, Type H and Type FVC Constant Torque 400/460 Vac
Three-Phase Input with Three-Phase Output
Switching Frequency: ATV58
U18N4 to D46N4 at 4 kHz, ATV58

·

D54N4 to D79N4 at 2 kHz

Drive Controller

Catalog Number

Motor Power

Rated

Output

Current

In

Input Line Current

5000 AIC

10000 AIC

22000 AIC

w/ Additional 3%

Line Impedance

400 V

kW

460 V

HP

A

400 V

A

460 V

A

400 V

A

460 V

A

400 V

A

460 V

A

400 V

A

460 V

A

ATV58HU18N4•

0.75

1

2.3

3.4

2.6

1.9

1.6

ATV58HU29N4•

1.5

2

4.1

6

4.5

3.3

3

ATV58HU41N4•

2.2

3

5.8

7.8

6

4.8

4.2

ATV58HU54N4•

3

4

7.8

10.2

7.8

6.3

5.6

ATV58HU72N4•

4

5

10.5

13

10.1

8.6

7.2

ATV58HU90N4•

5.5

7.5

13

17

13.2

11.8

10.1

ATV58HD12N4•

7.5

10

17.6

20.7

18.2

22.7

19.9

26.5

21

16

13.2

ATV58HD16N4•

11

15

24.2

28.8

25.3

31.4

27.6

35.4

28

23.6

19.5

ATV58HD23N4•

15

20

33

36.5

32

39.6

34.7

44.7

35.6

30.6

25.8

ATV58HD28N4•

18.5

25

40.7

37.3

38.3

37.9

39.2

38.9

40.1

38.7

40

ATV58HD33N4•

22

30

48.4

44.4

44.8

45.9

46.7

46.5

47.6

46.4

47.6

ATV58HD46N4•

30

40

66

59.1

59.9

61.2

61.9

62

61.9

62.1

63.7

ATV58HD54N4•

37

50

79.2

70.6

71.4

73.3

74.7

74.7

74.7

74.9

76.3

ATV58HD64N4•

45

60

93.5

84.3

84.8

88.8

89.7

92.3

89.7

92.3

93.8

ATV58HD79N4•

55

75

115.5

102.7

103.3

106.4

108.6

111.6

108.6

112.1

112.7

Ratings for Input Line Currents, Type H Variable Torque Low Noise 400/460 Vac
Three-Phase Input with Three-Phase Output
Switching Frequency: ATV58HU18N4 to D46N4 at 8 kHz, ATV58HD54N4 to D79N4 at 4 kHz

Drive Controller

Catalog Number

Motor Power

Rated

Output

Current

In

Input Line Current

5000 AIC

10000 AIC

22000 AIC

w/ Additional 3%

Line Impedance

22000 AIC

400 V

kW

460 V

HP

A

400 V

A

460 V

A

400 V

A

460 V

A

400 V

A

460 V

A

400 V

A

460 V

A

ATV58HU18N4•

0.75

1

2.1

3.2

2.8

1.9

1.6

ATV58HU29N4•

1.5

2

3.4

5.5

4.8

3.3

3

ATV58HU41N4•

2.2

3

4.8

7.4

6.5

4.8

4.2

ATV58HU54N4X•

5

7.6

10

7.5

ATV58HU72N4X•

7.5

11

14.3

9.9

ATV58HU90N4X•

10

14

18.1

13.1

ATV58HD12N4X•

15

21

25.8

19.6

ATV58HD16N4X•

20

27

32.4

25.9

ATV58HD23N4X•

25

34

38.9

31.1

ATV58HD28N4•

18.5

25

34

36.3

32.7

36.9

33.4

37.4

34.1

37.6

34

ATV58HD33N4•

22

30

40

43.3

39

44.2

40.1

45.1

40.4

44.7

40.4

ATV58HD46N4•

30

40

52

56.9

51

58.5

52.8

60.3

54.5

60.2

54.3

ATV58HD54N4•

37

50

65

70.2

61.5

71.9

64.9

73.6

67

73.4

67

ATV58HD64N4•

45

60

77

84

74.4

88.8

79.8

91.8

82.8

91.8

82.5

ATV58HD79N4•

55

75

96

102.8

91.7

106.9

96.4

112.6

100.5

112.3

100

This product is for 460 Vac applications at 5000 AIC. A line reactor (3% minimum) must be used at higher AIC ratings. See the
following table for 400 Vac rated controllers in this range.

NOTE: The input
conductor ampacity
rating should not be
less than the
ampacity rating
selected based on the
rated controller output
current.