Altivar, 58 trx ac drives, Wiring recommendations – Schneider Electric ALTIVAR 58 TRX User Manual

Page 102

Advertising
background image

Altivar

®

58 TRX AC Drives

Wiring Recommendations

©

2000–2003 Schneider Electric All Rights Reserved

102

09/2003

Ratings for Input Line Currents, Type H Variable Torque 208/230 Vac
Three-Phase Input with Three-Phase Output
Switching Frequency: ATV58HU29M2 to D23M2 at 4 kHz, ATV58HD28M2 to D46M2 at 2 kHz

Drive Controller

Catalog Number

Motor Power

208/230 Vac

Rated

Output

Current

In

Input Line Current

5000 AIC

10000 AIC

22000 AIC

w/ Additional 3%

Line Impedance

kW

HP

A

208 V

A

230 V

A

208 V

A

230 V

A

208 V

A

230 V

A

208 V

A

230 V

A

ATV58HU29M2•

1.5

2

7.5

9.4

8.6

6.6

5.9

ATV58HU41M2•

2.2

3

10.6

13

11.8

9.5

8.5

ATV58HU54M2•

3

4

14.3

17.2

15

12.6

11.2

ATV58HU72M2•

4

5

16.7

21.4

19.5

16.9

14.6

ATV58HU90M2•

5.5

7.5

24.2

29

26.4

32.1

28.4

34.7

30

23.3

20.6

ATV58HD12M2•

7.5

10

30.8

38.3

35

42.3

37.4

44.4

38.2

32.3

28.6

ATV58HD16M2•

11

15

46.2

41.7

37.8

41.7

38

41.7

38

41.7

38

ATV58HD16M2•

15

20

60

55.5

50.5

55.7

50.5

55.7

50.8

55.1

50.5

ATV58HD23M2•

18.5

25

75

67

61.8

67.2

61.8

67.2

61.8

67.1

61.4

ATV58HD28M2•

22

30

88

80.5

73.3

80.6

73.3

80.9

73.6

80.7

73.6

ATV58HD33M2•

30

40

116

107.6

97.9

108.4

97.9

108.4

98.5

107.6

98.5

ATV58HD46M2•

37

50

143

134.8

121.2

135.4

121.2

135.5

124

135

123.7

Ratings for Input Line Currents, Type H Variable Torque Low Noise 208/230 Vac
Three-Phase Input with Three-Phase Output
Switching Frequency: ATV58HU29M2 to D23M2 at 8 kHz, ATV58HD28M2 to D46M2 at 4 kHz

Drive Controller

Catalog Number

Motor Power

208/230 Vac

Rated

Output

Current

In

Input Line Current

5000 AIC

10000 AIC

22000 AIC

w/ Additional 3%

Line Impedance

kW

HP

A

208V

A

230 V

A

208 V

A

230 V

A

208 V

A

230 V

A

208 V

A

230 V

A

ATV58HU29M2•

1.5

2

7.5

9.4

8.6

6.6

5.9

ATV58HU41M2•

2.2

3

10.6

13

11.8

9.5

8.5

ATV58HU54M2•

3

4

14.3

17.2

15

12.6

11.2

ATV58HU72M2•

4

5

16.7

21.4

19.5

16.9

14.6

ATV58HU90M2•

5.5

7.5

24.2

29

26.4

32.1

28.4

34.7

30

23.3

20.7

ATV58HD12M2•

7.5

10

30.8

38.3

35

35.7

32.4

35.8

32.8

35.2

32.8

ATV58HD16M2•

11

15

46.2

42.7

39

42.7

39

42.7

39

42.4

39

ATV58HD23M2•

15

20

60

55.2

48.9

55.2

50.5

55.4

51.2

55.4

50.7

ATV58HD28M2•

18.5

25

75

67.8

61.9

68.2

62.1

68.4

62.6

67.6

61.6

ATV58HD33M2•

22

30

88

82

73.8

82

75.1

82.8

76.7

82.8

76.5

ATV58HD46M2•

30

40

116

108.6

97.3

109.2

99.2

109.7

99.7

109.4

99.7

NOTE: The input
conductor ampacity
rating should not be
less than the
ampacity rating
selected based on the
rated controller output
current.