Altivar, 58 trx ac drives, I/o extension cards – Schneider Electric ALTIVAR 58 TRX User Manual

Page 30

Advertising
background image

Altivar

®

58 TRX AC Drives

I/O Extension Cards

©

2000–2003 Schneider Electric All Rights Reserved

30

09/2003

The following table describes the functions and characteristics of the pump
switching option card control terminals.

NOTE: There is no +24 Vdc power supply output on this option card;
therefore, it is necessary to connect an external +24 Vdc power source
between terminals DO+ (+) and COMDI (-).

Function

Characteristics

Available DC Power Supplies
+10 and -10

Protected against short circuits and overloads
2 outputs, +10 Vdc and -10 Vdc
Maximum current = 10 mA each

Digital Logic Inputs
DI5, DI6, DI7

3 reassignable logic inputs. Impedance = 3.5 k

. Compatible with

Level 1 PLCs according to IEC 60065A-68. Maximum shielded
cable length: 330 ft (100 m).
Supply: +24 V (11 V min., 30 V max.)
State 0 if < 5 V, state 1 if > 11 V.
The logic inputs are sampled every 2 ms, maximum.

Logic Outputs
DO1, DO2, DO3, DO4

4 reassignable open collector logic output, compatible with Level 1
PLCs according to IEC 60065A-68.
Supply: +24 V (12 V min., 30 V max.),
maximum current = 200 mA each with external source.
The logic output is updated every 2 ms, maximum.

Analog Output
AO

1 reassignable 0

20 mA analog output

Maximum load impedance = 500

.

Resolution: 0.04 mA (9 bits)
Linearity: ± 0.1 mA
Accuracy: ± 0.2 mA
The analog output is updated every 2 ms, maximum.

Analog Input
AI3A, AI3B

1 reassignable, ±10 V bipolar differential input.
Input Impedance: AI3A to AI3B > 300 k

.

AI3A to COM

30 k

AI3B to COM > 600 k

Maximum allowable voltage: ± 30 V.
Frequency reference resolution: 0.1 Hz for 100 Hz (0.1% of
maximum frequency), 10 bits plus sign.
Accuracy: ± 0.5%.
Linearity: ± 0.2% of the maximum output frequency.
The analog input is sampled every 2 ms, maximum.
Maximum length of shielded cable: 66 ft (20 m).

COM

0 Vdc
Common for analog input signal

COM DI

0 Vdc
Common for logic inputs, logic outputs, and analog output

External Logic Output Power
DO+

Input: +24 Vdc nominal (12 Vdc min., 30 Vdc max.)
Maximum current = 200 mA per logic output.

[1] Maximum wire size capacity 1.5 mm

2

(AWG 14).

Recommended tightening torque is 3.54 lb-in (0.4 N•m).

COM

AI3A

AI3B

-10

+10

AO

COMDI

DO1

DO2

DO3

DI5

DI6

DI7

DO4

DO+

VW3A58210

Terminals for the
Pump Switching Option Card

T

e

rm

in

al

L

o

c

a

ti

ons

.e

ps

Advertising