Class 8998 Motor Control Centers

Space Requirements

216

09/2003

©

2000–2003 Schneider Electric All Rights Reserved

Constant Torque 208/240 Vac Altivar 58 TRX AC Drives

NEMA Type 1 and 1A
(Gasketed)

NEMA Type 12

Motor Rated Horsepower
200 / 230 Vac

Maximum Continuous
Output Current (A)

Space (Height)

Space (Height)

1 to 3 hp

11

12”

24”

5 hp

18

15”

24”

7.5 to 10 hp

31

24”

36”

15 to 20 hp

60

45”

45”

25 to 40 hp

116

72” (20” wide)

72” (20” wide)

Variable Torque, Low Noise 480 Vac Altivar 58 TRX AC Drives

NEMA Type 1 and 1A
(Gasketed)

NEMA Type 12

Motor Rated Horsepower
460 Vac

Maximum Continuous
Output Current (A)

Space (Height)

Space (Height)

0.5 to 3 hp

5.8

12”

24”

5 to 7.5 hp

13

15”

24”

10 to 15 hp

24

24”

36”

20 hp

33

27”

36”

25 to 40 hp

52

45”

45”

50 to 75 hp

96

72” (20” wide)

72” (20” wide)

Variable Torque, Low Noise 208/240 Vac Altivar 58 TRX AC Drives

NEMA Type 1 and 1A
(Gasketed)

NEMA Type 12

Motor Rated Horsepower
200 / 230 Vac

Maximum Continuous
Output Current (A)

Space (Height)

Space (Height)

1 to 3 hp

11

12”

24”

5 hp

18

15”

24”

7.5 to 10 hp

31

24”

36”

15 to 20 hp

60

45”

45”

25 to 40 hp

116

72” (20” wide)

72” (20” wide)