Altivar, 58 trx ac drives, Wiring recommendations – Schneider Electric ALTIVAR 58 TRX User Manual

Page 105

Advertising
background image

Altivar

®

58 TRX AC Drives

Wiring Recommendations

105

09/2003

©

2000–2003 Schneider Electric All Rights Reserved

Ratings for Input Line Currents, Type N 208 to 230 Vac
Single-Phase Input with Three-Phase Output / Three-Phase Input with Three-Phase Output

Ratings for Input Line Currents, Types E and F 200 Vac -10% / 240 Vac +10%
Three-Phase Input with Three-Phase Output

Drive Controller

Catalog Number

Motor Power at 4 kHz
Switching Frequency

Rated

Output

Current (In)

Input Line Current

5000 AIC

with Additional 3%

Line Impedance

kW

HP

A

200 V

A

240 V

A

200 V

A

240 V

A

ATV58EU29M2ZU

1.5

2

7.8

9.7

8.3

6.6

5.9

ATV58EU41M2ZU

2.2

3

11

13.4

11.4

9.5

8.5

Ratings for Input Line Currents, Types E and F 400 Vac -15% / 460 Vac +20%
Three-Phase Input with Three-Phase Output

Drive Controller
Catalog Number

Motor Power at 4 kHz
Switching Frequency

Rated
Output
Current
(In)

Input Line Current

5000 AIC

with Additional 3%
Line Impedance

400 V
kW

460 V
HP

A

400 V
A

460 V
A

400 V
A

460 V
A

ATV58EU18N4ZU

0.75

1

2.3

3.4

2.6

1.9

1.6

ATV58EU29N4ZU

1.5

2

4.1

6

4.5

3.3

3

ATV58EU41N4ZU

2.2

3

5.8

7.8

6

4.8

4.2

ATV58EU54N4ZU

3

7.8

10.2

7.8

6.3

5.6

ATV58EU72N4ZU

4

5

10.5

13

10.1

8.6

7.2

ATV58EU90N4ZU

5.5

7.5

13

17

13.2

11.8

10.1

208 to 230 Vac, Single-Phase Input with 3-Phase Output

Drive Controller Catalog Number

Dissipated Power at Rated
Load (Total)

Short Circuit Rating

Input Line Current

W

A RMS sym.

A

A

ATV58NU09M2•

42

2,000

5.6

4.7

ATV58NU18M2•

64

2,000

9.8

8.3

ATV58NU29M2•

107

5,000

18.5

15.6

ATV58NU41M2•

160

5,000

25.6

21.6

When these drive controllers are used with a single-phase input, a line reactor (3% minimum) must be used.

208 to 230 Vac, 3-Phase Input with 3-Phase Output

Drive Controller Catalog Number

Dissipated Power at Rated
Load (Total)

Short Circuit Rating

Input Line Current

W

A RMS sym.

A

A

ATV58NU29M2•

107

5,000

9.7

8.3

ATV58NU41M2•

160

5,000

13.4

11.4

ATV58NU54M2•

190

5,000

17.2

15

ATV58NU72M2•

240

5,000

22.4

19.5

NOTE: The input
conductor ampacity
rating should not be
less than the
ampacity rating
selected based on the
rated controller output
current.