Altivar, 58 trx ac drives, Communication parameters – Schneider Electric ALTIVAR 58 TRX User Manual

Page 90: Special drivecom registers, Monitoring registers (continued)

Advertising
background image

Altivar

®

58 TRX AC Drives

Communication Parameters

©

2000–2003 Schneider Electric All Rights Reserved

90

09/2003

W489
or 16#5FE8/28

USPL

0.01

Lower byte of machine speed

Value read

W490
or 16#5FE8/29

USPH

0.01

Upper byte of machine speed

Value read

W491
or 16#5FE8/2A

OPR

1%

Output power estimated by the
drive controller

Value read
100% corresponds to nominal motor power

W492
or 16#5FE8/2B

AO1R

0.002 mA

Image of analog output AO1.

Write authorized if AO1 = No (not assigned):
0 to 10000 (0 to 20 mA)
Read only if assigned: Value read

W493
or 16#5FE8/2C

UOP

0.1 V

Voltage applied to the motor.
Exists only on Type FVC models.

Value read

W494
or 16#5FE8/2D

APH

1 kWh
or
1 MWh

Drive power meter (kWh)

Value read.
If bit 15 = 0, units are kWh as given by bits 0 to 14.
If bit 15 = 1, units are MWh as given by bits 0 to 14.

W495
or 16#5FE8/2E

RTH

1 hr

Total motor run time

Value read

Special DRIVECOM Registers

Word

Code

Units

Parameter Name and Description

Possible Values or Range

W600
or 16#603F

ERRD

ErrorCode
Fault code
Read/Write

16#0 = NOF: No fault
16#1000 = CRF: Pre-charge relay fault
or = OLF: Motor overload (calculation or PTC probes)
or = SOF: Overspeed
16#2310 = OCF: Overcurrent (prolonged LIC)
16#2320 = SCF: Motor short-circuit (phase/earth)
16#3110 = OSF: Line supply overvoltage
16#3120 = USF: Line supply undervoltage (> 200 ms)
16#3130 = PHF: Line supply phase loss (> 1s)
16#3310 = OBF: DC bus overvoltage
or = OPF: Motor phase loss
16#4210 = OHF: Drive overheating (heatsink)
16#4310 = OTF: Motor overheating (PTC probes)
16#5520 = EEF: EEPROM memory fault
16#6100 = INF: Internal fault
16#6300 = CFF: Configuration incorrect (on initialization)
or = CFI: Configuration invalid (if writing a configuration)
16#7300 = ANF: Ramp not followed
or = LFF: Loss of 4–20 mA signal
or = TSF: Thermal sensor fault
16#7310 = SPF: Speed feedback missing or miswired
16#7510 = SLF: Serial link fault—keypad port (link break)
16#7520 = ILF: Fast serial link fault—options port (link break)
or = CNF: Fast serial link communication network fault
16#9000 = EPF: External fault

W601
or 16#6040

CMDD

Controlword
Command word—same as parameter CMD
Read/Write

W602
or 16#6041

ETAD

Statusword
Status word—same as parameter ETA
Write prohibited

W603
or 16#6042

LFRD

1 rpm

[1]

SpeedSetP
Speed reference in rpm (reference not peak
limited)
Read/Write

–32768 to 32767

W604
or 16#6043

FRHD

1 rpm

SpeedRef
Ramp output (signed) in rpm
Write prohibited

W605
or 16#6044

RFRD

1 rpm

[1]

SpeedActV
Motor speed in rpm
Write prohibited

W606
or 16#6046/1

SMIL

1 rpm

SpdMinMax
Minimum speed in 32 bits
Equivalent to LSP (W251), but in rpm
Read/Write

0 to HSP

W607

SMIH

Reserved

0

W608
or 16#6046/2

SMAL

1 rpm

SpdMinMax
Maximum speed in 32 bits
Equivalent to HSP (W250), but in rpm

Read/Write

LSP to TFR

W609

SMAH

Reserved

0

[1]

For ATV58 Type FVC, if CMI Bit 9 = 0, units are in rpm; if CMI Bit 9 = 1, units are in 0.015 Hz.

Monitoring Registers (Continued)

Word

Code

Units

Description

Possible Values or Range

Advertising