Using a line contactor or an output contactor, Altivar, 58 trx ac drives – Schneider Electric ALTIVAR 58 TRX User Manual

Page 107: Wiring recommendations, Wiring diagram for output contactor

Advertising
background image

Altivar

®

58 TRX AC Drives

Wiring Recommendations

107

09/2003

©

2000–2003 Schneider Electric All Rights Reserved

Using a Line Contactor or an Output Contactor

When controlling the power with a line isolation contactor, avoid frequently
opening and closing the line contactor as this could cause premature failure
of the drive controller. Use inputs LI1 to LI4 to start and stop the drive
controller. Limit operations of the line contactor to less than once per minute.

To use an output contactor, use the wiring diagram to the left for guidance
and set relay R2 to the Output Contactor Command function. In the wiring
diagram at left, the shaded portion is to be added to the output of either the
single-phase wiring diagram or the three-phase wiring diagram on page 108.

The recommended output contactors are shown in the table below.

KM2

KM2

ATV58H•••••

LC1-

ATV58H•••••

LC1-

U09M2

D25

U18N4

D25

U18M2

D25

U29N4

D25

U29M2

D25

U41N4

D25

U41M2

D25

U72N4

D25

U72M2

D25

U90N4

D25

U90M2

D25

D12N4

D25

D12M2

D32

D16N4

D25

D23N4

D4011

D16M2

D40

D28N4

D40

D23M2

D80

D33N4

D50

D28M2

D80

D46N4

D80

D33M2

D80

D54N4

D8010

D46M2

F115

D64N4

F115

D79N4

F115

Refer to the Digest for control voltage information.

U

V

W

U1

W1

V1

M

3 Phase

R2A

KM2

R2C

KM2

TS

120 VAC

TS = Transient suppressor

LineCont.eps

Wiring Diagram for Output Contactor

See Specifications section for
contactor ratings.